CHAPTER 4 - SETTING THE SSW-07
27
English
4.2 KICK START
4.3 INITIAL
VOLTAGE
SETTING
Kick Start Enabling
DIP Switch
Figure 4.2 - Kick Start enabling
Soft-Starter SSW-07 offers a Kick Start function for loads that
present a large initial resistance to movement.
This function is enabled through the Kick Start DIP Switch. The
duration of the voltage pulse is set through the trimpot Kick Start
Time.
Thevoltagepulseappliedisof80%Unduringtheprogrammed
trimpot Kick Start Time.
NOTE!
Usethisfunctiononlyforspecicapplicationsandwherenecessary.
Set the initial voltage to a value that the motor starts to run as soon
as the start command is given to the SSW-07.
The dot indicates
the factory default
setting
Initial Voltage
Setting Trimpot
Figure 4.3 - Initial voltage setting