3) Discharge Depth
Select “3. Discharge Depth” and press “OK” to enter discharge depth interface.
Discharge Depth
50%
EPS Discharge Depth
80%
Press up” or down” to change the 1
st
digit, press “ok” to switch to next digit. Input the value of Discharge Depth &
EPS Discharge Depth per battery specification. Press “OK”.
For example: if Discharge Depth = 50% & EPS Discharge Depth = 80%.
While grid is connected: WKS I inverter won’t discharge the battery when its SOC is less than 50%.
In case of blackout: WKS I inverter will work in EPS mode (if EPS mode is enabled) & keep discharging the battery
till battery SOC is less than 20%.
4) Max. Charge (A)
Select “4. Max. Charge (A)” and press “OK”. Press “up” or down” to change the 1
st
digit, press “ok” to switch to next
digit. Input the value of Max. Charge (A) per battery specification. Press “OK”.
5) *Over (V) Protection (only for DEFAULT battery type)
Select 5. Over (V) Protection” and press “OK. Press “up” or down” to change the 1
st
digit, press “ok” to switch to
next digit. Input the value of Over (V) Protection per battery specification. Press “OK”.
6) *Max. Charge (V) (only for DEFAULT battery type)
Select “6. Max. Charge (V)” and press “OK”. Press “up” or down” to change the 1st digit, press “ok” to switch to
next digit. Input the value of Max. Charge (V) per battery specification. Press “OK”.
7) Max. Discharge (A)
Select “7. Max. Discharge (A)” and press OK. Press “up” or down” to change the 1
st
digit, press ok” to switch to
next digit. Input the value of Max. Discharge (A) per battery specification. Press “OK”.
8) *Low (V) Protection (only for DEFAULT battery type)
Select 8. Low (V) Protection” and press “OK”. Press “up” or “down” to change the 1
st
digit, press ok” to switch to
next digit. Input the value of Low (V) Protection per battery specification. Press “OK”.
9) *Min. Discharge (V) (only for DEFAULT battery type)
Select “9. Min. Discharge (V)” and press “OK”. Press “up” or down” to change the 1
st
digit, press “ok” to switch to
next digit. Input the value of Min. Discharge (V) per battery specification. Press “OK”.
10) * Empty Discharged (V) (only for DEFAULT battery type)
Select “10. Empty Discharged (V)” and press “OK”. Press “up” or down” to change the 1
st
digit, press ok” to switch
to next digit. Input the value of Empty Discharged Voltage per battery specification. Press “OK”.