24.Parameterdescription
If there is no longer a heat demand from the heating circuit, the internal appliance
pump runs on for the set amount of time, to prevent a boiler safety shutdown
due to high temperatures.
Parameter HG07
Run-on time, heating circuit pump
Factory setting: see table
Setting range: 0 to 30 min
Individualsetting:_____
This function sets an upper limit on the boiler water temperature in heating
mode and the burner shuts down. This parameter has no function during cyl-
inder heating, and the boiler water temperature may also be higher during this
time. "Reheating effects" can result in the temperature being slightly exceeded.
Parameter HG08
Maximum boiler water temperature
HZ TV-max.
Factory setting: see table
Setting range: 40 to 90 °C
Individualsetting:_____
Each time the burner is shut down in heating mode, it will be disabled for the
duration of the burner cycle block. The burner cycle block is reset by switching
theON/OFFswitchOFFandONorbybrieypressingtheresetbutton.
Parameter HG09
Burner cycle block
Factory setting: see table
Setting range: 1 to 30 min
Individualsetting:_____
If multiple heat generators are controlled in one heating system with a cas-
cade module, addresses must be assigned to each heat generator. Each heat
generator requires its own eBUS address in order to communicate with the
cascade module. The activation sequence of the heat generators can be set
in the cascade module.
Please note: Duplicated addresses lead to malfunctions of the heating system.
Parameter HG10
eBUS address of the heat generator
Factory setting: see table
Setting range: 1 to 5
Individualsetting:_____
In this parameter, the gas type used for the gas condensing boiler can be set
to Nat. Gas (natural gas) or LPG (liquid propane gas).
The gas valve must be adjusted at the same time (1 = natural gas, 2 = LPG).
Parameter HG12
Gas type of the heat generator
Factory setting: see table
Setting range: Nat. or LPG
Individualsetting:_____