3064810_201804 97
Fault
code
Warning Possible causes Remedy
1 Burner control unit
replaced
The PCB has detected that the burner
control unit has been replaced
Ensure that the correct boiler coding card has
been inserted.
Check appliance parameter settings.
2 Heating circuit pressure Water pressure has fallen
below warning limit
Check the system pressure,
test sensors
3 Parameter changed Another boiler coding card has been
inserted. All parameters have been reset
to the factory setting; PCB HCM-2 or
GBCe has been replaced
Ensure that the correct
boiler coding card is inserted.
Check appliance parameter settings.
4 Noameestablished Noamewasdetected
at the last start attempt
of the burner.
Wait for more start attempts.
Check the ignition electrode and ignition
transformer.
Check the monitoring electrode.
Check the gas supply pressure.
5 Flame failure during
stabilisation time
Flame failure after
safety time
Flame failure during operation Check/replace monitoring electrode,
uegaspathblocked,
Condensate drain blocked,
Check the gas supply pressure.
24 Speed below or above
limit
Fan speed does not reach
set speed or
standstill
Checkuesystem,PWMand
power cable to fan
Check connection between CGBe and HCM-2
43 Many burner starts Excessive number of burner starts Inadequate heat transfer:
Ensure adequate heat transfer.
(Open radiators).
Increase burner cycle block HG09
53 IO control deviation Gas valve faulty
Gas supply pressure outside set range
Ionisation electrode corroded/bent
Current controller on GBC-e faulty
Gas valve power supply faulty
Burner earthing faulty
Gas valve:
- Check cables, plugs, power supply and
switching.
Gas pressure:
- Check gas supply pressure (flow pressure);
if OK,
Ionisation electrode:
- Check the condition of the electrode, clean
or replace if necessary.
- Adjust gap and position or replace if neces-
sary.
Replace GBC-e PCB,
as current controller possibly faulty.
Press reset button.
42.Troubleshootingwarningmessages