EasyManua.ls Logo

Wolf CGB-2-24 - Filling and Draining the System; Heating Water Treatment and Filling

Wolf CGB-2-24
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
52 3064810_201804
25.Fillingtheheatingsystem/trap
Beforecommissioning,carryoutaleaktestonallhydraulicpipework
Iftheapplianceisnotwatertight,thereisariskofleaksandresulting
materialdamage.
Testpressureontheheatingwatersidemax.4bar
Priortotesting,closetheshut-offvalvesintheheatingcircuitforthe
appliance,asotherwise,thesafetyvalve(accessory)opensat3bar.
Theappliancehasalreadybeenleaktestedatthefactoryat4.5bar.
TreatmentofheatingwaterinaccordancewithVDI2035:
Potablewatermaybeusedasllingandtop-upwaterifthelimitsintable1arenot
exceeded. Otherwise, the water must be treated using a desalinisation process.
If the water quality does not meet the required values, the warranty for components
on the water side becomes void.
Theonlypermissiblewatertreatmentprocessisdesalinisation!
Thoroughlyushthesystempriortocommissioning.Inordertokeepoxygenation
aslowaspossible,itisrecommendedtoushthesystemusingtapwaterandthen
tousethiswaterforthewatertreatment(positionthedirtlterupstreamoftheion
exchanger).
Heatingwateradditivessuchasantifreezeorinhibitorsarenot
permitted,astheycandamagetheheatingwaterheatexchanger.
Alkalisingadditivesmaybeusedbyawatertreatmentspecialistto
stabilisethepHvalue.
In order to prevent corrosion damage to the aluminium heating water heat exchanger,
the pH value of the heating water must be between 6.5 and 9.0.
Inmixedinstallations,apHvalueof8.2to9.0mustbemaintainedin
accordancewithVDI2035.
The pH value should be checked again 8-12 weeks after commissioning, as under
certain circumstances, chemical reactions may cause it to change. If it does not fall
within this range after 8-12 weeks, remedial measures must be taken.
Heating water quality requirement relating to the entire heating system
LimitsinrelationtospecicsystemvolumeVA
(VA=systemvolume/max.ratedheatingoutput
1)
)
Totalhardnessconversion:1mol/m³=5.6°dH=10°fH
Total
heating
output
V
A
≤20l/kW V
A
> 20 l/kW and < 50 l/kW V
A
≥50l/kW
Total hardness / total
alkaline earths
Conduc-
tivity
2)
at 25°C
Total hardness / total
alkaline earths
Conduc-
tivity
2)
at 25°C
Total hardness /
total alkaline earths
Conduc-
tivity
2)
at 25°C
[kW] [°dH] [mol/m³] C [µS/cm] [°dH] [mol/m³] C [µS/cm] [°dH] [mol/m³] C [µS/cm]
1 ≤50 ≤16.8 ≤3.0 < 800 ≤11.2 ≤2 < 800 ≤0.11
3)
≤0.02 < 800
2 50-200 ≤11.2 ≤2
< 100
≤8.4 ≤1.5
< 100
≤0.11
3)
≤0.02
< 1003 200-600 ≤8.4 ≤1.5 ≤0.11
3)
≤0.02 ≤0.11
3)
≤0.02
4 ≤600 ≤0.11
3)
≤0.02 ≤0.11
3)
≤0.02 ≤0.11
3)
≤0.02
Thetotalamountofllandtop-upwateroverthelifecycleoftheboilermustnotexceedthreetimesthenominalvolumeofthe
heating system.
1)
According to VDI 2035, in systems with multiple boilers, use the maximum rated heating output of the smallest heat source
2)
High salinity < 800 µS/cm
Low salinity < 100 µS/cm
3)
< 0,11°dH recommended standard; permissible up to limit of < 1°dH
Table 1
Hydraulics
Please
note
Filling
Please
note
Please
note
Filling
Please
note
Electricalconductivityandwater
hardness

Other manuals for Wolf CGB-2-24

Related product manuals