3064810_201804 67
34. Highefciencypumpfunction
description
Factorysettingsforpumpspeeds
Troubleshooting
Appliance
output
Heating mode DHW Standby
heating mode
maximum minimum
14 kW 70 % 45 % 55 % 30 %
20 kW 70 % 45 % 75 % 30 %
24 kW 70 % 45 % 85 % 30 %
Problem Remedy
Individual radiators do not warm up
properly.
Carry out hydraulic balancing, i.e.
reducetheowrateofhotterradiators.
Increase the pump speed (HG16).
In the spring and autumn, the required
room temperature is not achieved.
Increase the set room temperature at
the controller, e.g. with set value setting
±4.
The required room temperature is not
achieved when outside temperatures
are very low.
Select a steeper heating curve at
thecontroller,e.g.increasetheow
temperature at standard outside
temperatures.