41.Troubleshooting
Fault
code
Fault Possiblecauses Remedy
05 Flame failure Flamefailureduringamestabilisation
afteramedetection
Monitoring electrode faulty
Flue path blocked
Condensate drain blocked
Gas type setting
Gas pressure
Flue gas recirculation
(uegasinventilationair)
Gas condensing boiler contaminated
Gas type setting:
- Check gas type setting on the gas valve
and the AM/BM.
Gas pressure:
- Check the gas supply pressure (flow pres-
sure).
Ionisation electrode:
- Check the condition of the electrode,
clean or replace if necessary.
- Set gap and position or
replace if necessary.
Flue gas recirculation:
- Check the flue path inside and outside the
appliance (leaking, blocked).
Press reset button.
06 TL excess temp. One of the temperature sensors
eHLSC1 or eHLSC2 has exceeded the
limit of the temperature limiter (102 °C)
System pressure
Air in heating circuit
Temperaturelimiterintheow
Pump
Check system pressure.
Vent heating circuit.
Temperature limiter in the flow:
- Check leads and plug-in connections.
- If electrical connection OK and no func-
tion, replace temperature limiter.
Pump:
- Check if pump is running.
- If not, check cables and plugs.
- If electrical connection OK and no func-
tion: Replace pump
Press reset button.
07 Flue gas TL, excess
temperature
Theuegastemperaturehasexceeded
theuegastemperaturelimiter's
shutdown temperature of 110 °C
Combustion chamber module
Combustion chamber
Flue gas temperature limiter
Combustion chamber module:
- Check installation position.
Combustion chamber:
- If the combustion chamber is heavily
contaminated, carry out maintenance or
replace.
Flue gas temperature limiter:
- Check leads and plug-in connections.
- If electrical connection OK and no func-
tion: Replace temperature limiter.
08 Flue gas damper does
not switch
Flue gas damper contact (E1) closes or
does not open on demand; output A1
doesnotswitchuegasdamper;ue
gas damper blocked
Flue gas damper:
- Check cables, plug-in connections and
power supply.
- Check the flue gas damper function.
- Check flue gas damper feedback.
- Check settings HG13 and HG14.
Press reset button.
255 Fault code unknown This fault is not known in this software Check software version of the PCBs.
Call a contractor
10 eHLSC sensor faulty Temperature sensor eHLSC1, eHLSC2
on the combustion chamber or sensor
lead has short circuit or break
eHLSC on the combustion chamber:
- Check leads and plug-in connections.
- If electrical connection OK and no func-
tion, replace eHLSC.
11 Flame pretence Flame signal is detected when burner
is off
Check monitoring electrode.
Press reset button.