EasyManuals Logo

Worcester GREENSTAR HIGHFLOW 440CDI ERP Installation, Commissioning And Servicing Instructions

Worcester GREENSTAR HIGHFLOW 440CDI ERP
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
SERVICING AND SPARES
6720818077 (2016/04) - Greenstar Highflow CDi
ErP
37
If further adjustment is required, remove the combustion chamber
cover and set adjuster [3] as necessary
Replace the cover and check the maximum CO
2
again
Fig. 57 Setting air/gas ratio
To set the minimum CO
2
:
Turn the temperature control [2] to minimum. This will make the
boiler go to minimum output, allow the output to settle for
approximately 10 minutes
Remove the dust cap and adjust [4] on the gas valve
Measure the minimum CO
2
and compare with the minimum output
shown on the table 15
Check that the CO is less than 200ppm
Repeat the procedure until the correct output is achieved
Confirm the maximum CO
2
Turn temperature control to maximum output and recheck the CO
2
.
If correct, hold down the Service engineer button [1] for two
seconds, the boiler should return to normal operating mode with the
blue power indicator permanently illuminated
Remove the flue gas analyser
Replace the cap over the flue gas sample point
Remove the combustion chamber cover
Replace the dust cover over the minimum output adjuster [4]
Replace plastic cover to maximum outlet adjuster [3]
Replace the combustion chamber cover
6.9 Replacement parts
6.9.1 Draining the appliance
Turn off the system heating flow and return isolation valves - external
to boiler.
Unscrew the tank drain cap from the tank drain valve [1].
Connect the hose connection and nut [4] (supplied with boiler,
literature pack) to the tank drain valve [2].
Attach a suitable hose [5], to the hose connector at the tank drain
valve and route the other end of the hose to an external drain point.
Fully open the drain tap [3] on the tank drain valve [1].
Close the drain tap [3] when the flow from the appliance has stopped
and remove the hose.
Fig. 58 Draining the boiler
GAS TYPE CO
2
setting max. CO
2
setting min.
The CO
2
should be measured after 10 minutes
Greenstar HF 440CDi
ErP
Natural Gas 9.4 ± 0.2% 8.6 ±0.2%
LPG (propane) 10.8 ± 0.2% 10.4 ±0.2%
Greenstar HF 550CDi
ErP
Natural Gas 9.4 ± 0.2% 9.0 ±0.2%
LPG (propane) 10.8 ± 0.2% 10.4 ±0.2%
CO - less than 200 ppm (0.002 ratio)
Table 15 CO/CO
2
settings
6720648568-42.1Wo
Max adjustment
Max mode
Service
mode
Min adjustment
Min mode
10 s10 s
1
2
2
4
3
CAUTION: Isolate the boiler
Turn off the gas supply and isolate the mains
electrical supply before starting any work and
observe all relevant safety precautions.
Drain the boiler/system where necessary and protect
any electrical equipment from water ingress during
component replacement.
NOTICE: Gaskets and O rings
Refit or replace any components removed from the
appliance in the reverse order using new gaskets/'O'
rings/sealant/heat transfer paste where necessary.
Any 'O' ring or gasket that appears damaged must be
replaced. Always check that any electrical
connections are correctly made and that all screws
are tight.
NOTICE: AFTER REPLACEMENT OF ANY
COMPONENTS ALWAYS CHECK FOR GAS
TIGHTNESS WHERE RELEVANT AND CARRY OUT
FUNCTIONAL CHECKS AS DESCRIBED IN THE
COMMISSIONING SECTION.
NOTICE: Service work
Any service work must be carried out by competent
registered gas engineer, such as a British Gas or
other GAS SAFE registered engineer.
After re-assembly the combustion must be checked
using the procedure in the section “Setting the air/
gas ratio”. Measurement and setting of the gas ratio
must not be attempted unless the person is equipped
with a combustion analyser conforming to BS 7927
and is competent in its use.
A small quantity of water may remain in some
components even after the appliance has been drained.
Protect any electrical components when removing
components from the water circuits.
6720818077-21.1Wo
2
3
1
4
5

Table of Contents

Other manuals for Worcester GREENSTAR HIGHFLOW 440CDI ERP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Worcester GREENSTAR HIGHFLOW 440CDI ERP and is the answer not in the manual?

Worcester GREENSTAR HIGHFLOW 440CDI ERP Specifications

General IconGeneral
ModelGreenstar Highflow 440CDi ErP
CategoryBoiler
TypeCombi
ErP RatingA
Hot Water Flow Rate20 l/min
Fuel TypeNatural Gas
Gas TypeNatural Gas
Warranty5 years
MountingWall Mounted

Related product manuals