Specifications
A2 975-0131-01-01
Electrical Specifications
Input
Output
Input voltage, Maximum Power Point range 195 to 550 Vdc
Absolute maximum array open circuit voltage 600 Vdc
Maximum input current 16.6 A DC
Maximum array short circuit current 19 A DC
Recommended PV array power Up to 3300 W
Reverse polarity protection Short circuit diode
Ground fault protection GF detection, I
DIF
> 1 A
GT3.0 North American GT3.0 European
Maximum output power 3000 W AC 3000 W AC
Nominal output power over rated temp range 2500 W AC 2500 W AC
Maximum utility backfeed current 20 A 20 A
Nominal output voltage 240 V 230 V
Operating range, utility voltage (default)*
* Requires Utility permission and qualified service personnel to change settings.
211 to 264 Vac 202 to 253 Vac
Nominal output frequency 60 Hz 50 Hz
Operating range, utility frequency (default)* 59.3 to 60.5 Hz 47.1 to 50.9 Hz
Maximum continuous output current 14.2 A 14.9 A
Output overcurrent protection 20 A RMS 20 A RMS
Total Harmonic Distortion (THD) <5% <5%
Power factor >0.9 >0.9
Utility monitoringislanding protection Vac, fac as per UL1741
Output characteristics Current source
Output current waveform Sine wave