Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 20
Uninterrupble Power Supply
3. The backup me may very from dierent environment temperature and load type.
4. The backup me depends on the quanty external baeries.
5. When seng backup me for 16.5 hours (default value from LCD panel), aer discharging 16.5 hours,
UPS will shut down automacally to protect the baery. This baery discharge protecon can be enabled
or disabled through LCD panel control. (Refer to 3.3 LCD Sengs secon)
Test the baeries
1. If you need to check the baery status when the UPS is running in AC mode/CVCF mode/ECO mode, you
could press the “Test” buon to let the UPS do baery self-test.
2. To keep the system reliable, the UPS will perform the baery self-test automacally periodically. The
default seng period is once per week.
3. Users also can set baery self-test through monitoring soware.
4. If the UPS is at baery self-test, the LCD display and buzzer indicaon will be the same as at Baery
mode except that the baery LED is ashing.
Turn o the UPS with ulity power supply in AC mode
1. Turn o the inverter of the UPS by pressing “OFF” buon for at least 0.5s, and then the buzzer will beep
once. The UPS will turn into Bypass mode.
NOTE 1: If the UPS has been set to enable the bypass output, it will bypass voltage from ulity power to output
terminal even though you have turned o the UPS (inverter).
NOTE 2: Aer turning o the UPS, please be aware that the UPS is working at Bypass mode and there is risk of
power loss for connected devices.
2. In Bypass mode, output voltage of the UPS is sll present. In order to cut o the output, switch o the
input breaker. A few seconds later, there is no display shown on the display panel and UPS is completely
o.
Turn o the UPS without ulity power supply in Baery mode
1. Turn o the UPS by pressing “OFF” buon for at least 0.5s, and then the buzzer will beep once.
2. Then UPS will cut o power to output and there is no display shown on the display panel.
Mute the buzzer
1. To mute the buzzer, please press the “Mute” buon for at least 0.5s. If you press it again aer the buzzer
is muted, the buzzer will beep again.
2. Some warning alarms can’t be muted unless the error is xed.
Operaon in warning status
1. When Fault LED ashes and the buzzer beeps once every second, it means that there are some prob-
lems for UPS operaon. Users can get the fault code from LCD panel. Please check the trouble shoong
table in secon 4 for details.
Operaon in Fault mode
1. When Fault LED illuminates and the buzzer beeps connuously, it means that there is a fatal error in the
UPS. Users can get the fault code from display panel. Please check the trouble shoong table in secon 4
for details.
2. Please check the loads, wiring, venlaon, ulity, baery and so on aer the fault occurs. Don’t try to
turn on the UPS again before solving the problems. If the problems can’t be xed, please contact the dis-
tributor or service people immediately.
3. For emergency case, please cut o the connecon from ulity, external baery, and output immediately
to avoid more risk or danger.