TX91 3.8- 10kVA User’s Manual
Page 21
Uninterrupble Power Supply
Adjusng charging current:
1. In bypass mode, press “Test/UP” buon and “Mute/Down” buon simultaneous for more than 1s to
enter the seng menu.
2. Press the “Mute/Down” buon unl it shows 17 in parameter 1 and press “Enter” buon to adjust the
charging current. (Check 3-7 LCD seng for the details.)
3. In parameter 2, you can select the charging current from 1A to 4A by pressing “Test/UP” buon or
“Mute/ Down” buon. Select the charging current based on the number of baery strings. One string
equals 1A, if the number of baery strings is 2 then set it to 2A, if the baery strings is 3A set it to 3A,
anything 4 strings or more set it to 4A.
4. Conrm the seng by pressing the “ON/Enter” buon.
5. In parameter 3, it is to adjust the charging current according to the deviaon between the actual charg-
ing current and the seng value of the current.
For example, you want to have the charging current in 4A, but in fact, the charging current is measured
only 3.6A. Then, you need to select “+” and change the number to 4 in parameter 3. It means the seng
charging current will be added 0.4A as output charging current. Then, conrm this modicaon by press-
ing “ON/Enter” buon. Now, you may press “Test/UP” and “Mute/Down” buons at the same me to exit
the seng mode.
NOTE 1: Be careful that the maximum charging current does not exceed the baery accepted charging current.
NOTE 2: All parameter sengs will be saved only when UPS shuts down normally with internal or external baery
connecon. (Normal UPS shutdown means turning o input breaker in bypass/no output mode).