TX91 3.8- 10kVA User’s Manual
Page 23
Uninterrupble Power Supply
15 programs available list for parameter 1:
Code Descripon Bypass AC ECO CVCF Baery Baery
Test
01 Output voltage Y
02 Output frequency Y
03 Voltage range for bypass Y
04 Frequency range for bypass Y
05 ECO mode enable/disable Y
06 Voltage range for ECO mode Y
07 ECO mode frequency range seng Y
08 Bypass mode seng Y
09 Baery backup me seng Y Y Y Y Y Y
10 Reserved Reserved for future
11 Reserved Reserved for future
12 Hot standby funcon enable/disable Y Y Y Y Y Y
13 Baery voltage adjustment Y Y Y Y Y Y
14 Charger voltage adjustment Y Y Y Y Y Y
15 Inverter voltage adjustment Y Y Y
16 Output voltage calibraon Y Y Y
17 Charging current seng Y Y Y Y Y Y
*Y means that this program can be set in this mode.
Note: All parameter sengs will be saved only when UPS shuts down normally with internal or external baery
connecon. (Normal UPS shutdown means turning o input breaker in bypass/no output mode).
01: Output voltage
Interface Seng
Parameter 3: Output voltage
You may choose the following output voltage in parameter 3:
208: Presents output voltage is 208Vac
220: Presents output voltage is 220Vac
230: Presents output voltage is 230Vac
240: Presents output voltage is 240Vac