Do not connect directly into an Ethernet port. The voltage destroys the Ethernet device.
NOTICE:
This RJ45 connector is not an Ethernet connection. Do not connect directly to an Ethernet
port.
1 876
54
32
WS003606
1. Not used
2. Not used
3. 0 V
4. Optibus -
5. Optibus +
6. +24 V, power supply for the remote key pad
7. RS485- Modbus RTU/CanOpen
8. RS485+ Modbus RTU/CanOpen
All SRC 311 parameters are read and set over the fieldbus communication. Process
parameters marked as setting is also accessed and read, but process parameters marked
as fixed value cannot be read or set over the fieldbus communication.
Any external system that wants to read process data and alarms from SRC 311 must be
configured with the correct parameter addresses for SmartRun
.