EasyManuals Logo
Home>Xylem>Controller>HYDROVAR HV2.1f

Xylem HYDROVAR HV2.1f User Manual

Xylem HYDROVAR HV2.1f
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #50 background imageLoading...
Page #50 background image
50
9.19 2
nd
Required Value
CONFIG. REQ. VAL.2
OFF
With this parameter a 2
nd
independent required value
can be selected and at the same time the source of it
will be determined.
The changeover between 1
st
and the 2
nd
required value can be done via the digital input,
terminal X1/14 on the control card. If this input is connected to Ground (X1/10), the 2
nd
required value will be active.
Possible settings with Ï or Ð:
OFF
2
nd
required value is not active (Using only standard set point)
INT
Internal 2
nd
required value, setting according to existing required value in
the main menu, but at closed digital input (X1/14).
EXT ADC-I
The 2
nd
required value is given from the value of a current signal
(4-20mA) connected to terminals X1/12, X1/10 (Ground).
Notice:
If the incoming current signal is below 4mA, an error message
will be shown on the display and a failure is indicated (failure relay is
closed). The failure is also shown at a multi pump layout, but no failure
would be indicated (failure relay is not closed) only the master-pump will
be exchanged. If the current signal fails at all HYDROVARs, the failure
would be indicated also.
EXT ADC-U 0-10V
or
EXT ADC-U 2-10V
The 2
nd
required value is given from the value of a voltage signal (0-10V
or 2-10V) connected to terminals X1/13, X1/10 (Ground).
The max. value of the analogue signal is equal to the defined SENSOR RANGE.
(see chapter 9.15)
Setting the 2
nd
required value:
The active required value is shown in the actual display of the parameter “Required value”.
If the 2
nd
required value is enabled (digital input, terminal X1/14, closed), there is shown
“Required value 2” in the first line.
The second line will shown the source of the 2
nd
required value, selected in the parameter
CONFIG. REQ VAL.2, and also the actual value of this input as well.
INT: setting according the existing required value in the main menu
EXT: only display of the value of the 2
nd
analogue input signal.
In case of saving, both required values will be saved automatically.
Press the ¾ button to change to the next parameter

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xylem HYDROVAR HV2.1f and is the answer not in the manual?

Xylem HYDROVAR HV2.1f Specifications

General IconGeneral
BrandXylem
ModelHYDROVAR HV2.1f
CategoryController
LanguageEnglish

Related product manuals