VAN-V17001E<1>, Replacing A1000 crane with CR700
12/44
3-2. Control Circuit Terminals, Signal Levels
Terminal function defaults differences between A1000 and CR700 are listed in the table below.
Control circuit
terminals
Name
Signal Level
A1000 CR700 A1000 CR700
S1 S1
Multi-function input 1
(&ORVHG: Forward run, 2SHQ: Stop)
Photocoupler
24 Vdc, 8 mA
Photocoupler
24 Vdc, 6 mA
S2 S2
Multi-function input 2
(&ORVHG: Reverse run, 2SHQ: Stop)
S3 S3
Multi-function input 3
(External fault (N.O.))
S4 S4
Multi-function input 4
(Fault reset)
S5 S5
Multi-function input 5
(Brake release check)
S6 S6
Multi-function input 6
(Multi-step speed reference 1)
S7 S7
Multi-function input 7
(Multi-step speed reference 2)
S8 S8
Multi-function input 8
(Baseblock command (N.C.))
SC
*1
SN 'LJLWDO input power supply 0 V
Photocoupler
24 Vdc, 8 mA
MFDI power supply, 24V
(max. 150 mA)
Note: Do not install a jumper
between terminals SP and
SN.
SC Multi-function input common
SP 'LJLWDO input power supply +24 Vdc
RP 0XOWLIXQFWLRQSXOVHWUDLQLQSXW
Response frequency
0.5 - N+]Nȍ
-
+V +V 3RZHUVXSSO\IRUDQDORJLQSXWV +10.5 V (allowable current 20 mA max.)
-V -V 3RZHUVXSSO\IRUDQDORJLQSXWV -10.5V (allowable current 20 mA max.)
A1 A1 Multi-function analog input 1
0-9Nȍ
0+/-10 V
0-9GFNȍ
0+/-10 V
4-P$ȍ
0-P$ȍ
A2 A2 Multi-function analog input 2
0-9GFNȍ
0+/-10 V
4-P$ȍ
0-P$ȍ
A3 A3 Multi-function analog input 3
0-9Nȍ
0+/-10 V
0-9GFNȍ
0+/-10 V
4-P$ȍ
0-P$ȍ
- Can be set for PTC input
AC AC Frequency reference common 0 V
E (G) E (G) *URXQGIRUVKLHOGHGOLQHVDQGRSWLRQFDUGV -
H1 H1 Safe Disable input 1
24 Vdc, 8 mA
Closed: Normal operation
Open: Coasting motor
,QWHUQDOLPSHGDQFHNȍ
OFF time of at least 1 ms
24 Vdc, 6 mA
Closed: Normal
operation
Open: Coasting motor
,QWHUQDOLPSHGDQFHNȍ
OFF time of at least 2 ms
H2 H2 Safe Disable input 2
HC HC Safe Disable function common
Safe Disable function
common
Safe Disable function
common
Note: Do not jumper or short
terminals HC and SN.
DM+
*2
Safety monitor output
+48 Vdc 50 mA max.
Connect to Multi-function
digital output, Multi-function
photocoupler output
DM-
*2
Safety monitor output

Other manuals for YASKAWA A1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 and is the answer not in the manual?

YASKAWA A1000 Specifications

General IconGeneral
TypeAC Drive
SeriesA1000
Input Voltage200-240V, 380-480V
Frequency Range0-400 Hz
Horsepower Range0.5 to 1000 HP
Power Range0.4 to 630 kW
Control MethodV/f Control
Overload Capacity150% for 60 seconds
BrakingDynamic Braking
CommunicationModbus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Operating Temperature-10 to +50°C
Storage Temperature-20 to 60°C
Humidity5 to 95% RH (non-condensing)
EnclosureIP20