Parameter Tables
5-37
H2: Multi-Function Contact Outputs
Multi-Function Contact Output Functions
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control
Methods
MEMO-
BUS
Register
Page
Display
V/f
Open
Loop
Vector
Flux
Vector
H2-01
Terminal M1 thru
M2 Function
Selection (Relay)
Multi-function contact output 0 to 37 0 No A A A 40BH -
Term M1-M2 Sel
H2-02
Terminal M3-M4
Function Selec-
tion (Relay)
Multi-function contact output 1 0 to 37 1 No A A A 40CH -
Term P1 Sel
H2-03
Terminal M5-M6
Function Selec-
tion (Relay)
Multi-function contact output 2 0 to 37 2 No A A A 40DH -
Term P2 Sel
H2-04
Terminal P3
Function Selec-
tion (Open Col-
lector)
Multi-function contact output 3 0 to 37 6 No A A A 40EH -
Term P3 Sel
H2-05
Terminal P4
Function Selec-
tion (Open Col-
lector)
Multi-function contact output 4 0 to 37 10 No A A A 40FH -
Term P4 Sel
Set
Value
Function
Control
Methods
Page
V/f
Open
Loop
Vector
Flux
Vector
0 During Run (ON: Run Command is on or voltage is being output) Yes Yes Yes 6-77
1 Zero-speed Yes Yes Yes 6-77
2 Frequency agree 1 (L4-02 used). Yes Yes Yes 6-45
3
Desired frequency agree 1 (ON: Output frequency = ±L4-01, L4-02 used and during
frequency agree)
Yes Yes Ye s 6 - 45
4
Frequency (FOUT) detection 1 (ON: +L4-01 ≥ output frequency ≥ -L4-01, L4-02
used)
Yes Yes Ye s 6 - 45
5
Frequency (FOUT) detection 2 (ON: Output frequency ≥ +L4-01 or output frequency
≤ -L4-01, L4-02 used)
Yes Yes Ye s 6 - 45
6
MxC operation ready
READY: After initialization, no faults
Yes Yes Ye s -
7 During detection of power voltage fault (FDV, AUV, or UV) Yes Yes Yes -
8 During baseblock (ON: during baseblock) Yes Yes Yes -
9 Frequency reference selection (ON: Frequency reference from Operator) Yes Yes Yes -
A Run Command selection status (ON: Run Command from Operator) Yes Yes Yes -
B
Overtorque/undertorque detection 1 NO (NO contact: Overtorque/undertorque detec-
tion at on)
Yes Yes Ye s 6 - 49
C Loss of frequency reference (Enabled when 1 is set for L4-05) Yes Yes Yes 6-64