6-18
* The setting range for accel/decel times depends on the setting of C1-10 (Accel/Decel Time Setting Units). If C1-10 is set to 0, the setting range is 0.00 to
600.00 (s).
Setting the Units to Express the Acceleration and Deceleration Time
Set the accel/decel time units using C1-10. The default setting for C1-10 is 1.
Switching Acceleration and Deceleration Time Using Multi-Function Input Terminal
Commands
The MxC allows for four separate acceleration times and four separate deceleration times. When the multi-
function input terminals (H1-) are set to 7 (Accel/Decel Time Selection 1) and 1A (Accel/Decel Time
Selection 2), the accel/decel time of the MxC can be changed even while the application is running based on
the terminal switch status.
The following table shows the possible accel/decel time switching combinations.
C2-01
S-Curve Charac-
teristic at Accel
Start
All sections of the S-curve characteristic time
are set in seconds units.
When the S-curve characteristic time is set,
the accel/decel times will increase by only
half of the S-curve characteristic times at start
and end.
0.00 to
2.50
0.20 s No A A A
SCrv Acc @ Start
C2-02
S-Curve Charac-
teristic at Accel
End
0.00 to
2.50
0.20 s No A A A
SCrv Acc @ End
C2-03
S-Curve Charac-
teristic at Decel
Start
0.00 to
2.50
0.20 s No A A A
SCrv Dec @ Start
C2-04
S-Curve Charac-
teristic at Decel
End
0.00 to
2.50
0.00 s No A A A
SCrv Dec @ End
Set value Details
0 The accel/decel time settings range is 0.00 to 600.00 in units of 0.01 s.
1 The accel/decel time settings range is 0.0 to 6000.0 in units of 0.1 s.
Accel/Decel Time
Selection 1 Terminal
Accel/Decel Time
Selection 2 Terminal
Acceleration Time Deceleration Time
off off C1-01 C1-02
on off C1-03 C1-04
off on C1-05 C1-06
on on C1-07 C1-08
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control Methods
Display
V/f
Open
Loop
Vector
Flux
Vector
Run Command
Output frequency
Time
on
off
C2-02 C2-03
C2-04
C2-01