7.5.5 External Terminal Functions: H
7-64
7.5.5 External Terminal Functions: H
This section describes the settings for the external terminal functions.
J
Multi-function Input Settings: H1
The settings and functions for the multi-function inputs are listed in Table 7.8.
Table 7.8 Multi-function Input Functions
Control Method
Setting
value
Function
V/f
V/f
w/
PG
Open
loop
Vector
Flux
vector
0
3-wire sequence (Forward/Reverse run command)
f f f f
1
Local/Remote selection (ON: Operator, OFF: Constant setting) f f f f
2
Option/Inverter selection (ON: Option card)
f f f f
3
Multi-step speed reference 1
When H3-05 is set to “0,” this function is combined with “Master/auxiliary speed switch.”
f f f f
4
Multi-step speed reference 2 f f f f
5
Multi-step speed reference 3
f f f f
6
Jog frequency reference (higher priority than multi-step speed reference)
f f f f
7
Accel/Decel time 1 f f f f
8
External baseblock NO (NO contact: Baseblock at ON)
f f f f
9
External baseblock NC (NC contact: Baseblock at OFF) f f f f
A
Accel/Decel ramp hold (ON: Accel/decel stopped, frequency on hold)
f f f f
B
OH2 alarm signal input (ON: OH2 will be displayed) f f f f
C
Multi-function analog input selection (ON: Enable)
f f f f
D
No V/f control with PG (ON: Speed feedback control disabled,) (normal V/f control)
×
f
× ×
E
Speed control integral reset (ON: Integral control disabled)
×
f
×
f
F
Not used.
10
Up command (Always set with the down command) f f f f
11
Down command (Always set with the up command)
f f f f
12
FJOG command (ON: Forward run at jog frequency d1-09)
f f f f
13
RJOG command (ON: Reverse run at jog frequency d1-09)
f f f f
14
Fault reset (Reset when turned ON)
f f f f
15
Emergency stop (when NO contact is ON: Deceleration to stop in emergency stop time C1-09)
f f f f
16
Motor switch command (Motor 2 selection)
f
f
17
Emergency stop (normally closed condition: Deceleration to stop in emergency stop time C1-09 when
OFF)
f
f
18
Timer function input (Functions are set with b4-01, b4-02 and the timer function is set at the same time)
f f f f
19
PID control disable (ON: PID control disabled) f f f f
1A
Accel/Decel time 2
f f f f
1B
Constants write enable (ON: All constants can be written-in. OFF: All constants other than frequency
monitor are write protected.)
f f f f
1C
Trim control increase (ON: d4-02 frequencies are added to analog frequency references.)
f f f f
1D
Trim control decrease (ON: d4-02 frequencies are subtracted from analog frequency references.) f f f f
1E
Analog frequency reference sample/hold f f f f
1F
Frequency reference terminal 13/14 selection (ON: selects terminal 14); valid only when H309=1F
f f f f
20 to
2F
External fault (Desired settings possible)
Input mode: NO contact/NC contact, Detection mode: Normal/during operation
Stopping method: Deceleration to stop, coast to stop, emergency stop or continue operation.
f f f f
30
PID control integral reset (ON: Reset)
f f f f
31
PID control integral hold (ON: Hold)
f f f f
60
DC injection braking command (ON: Performs DC injection braking)
f f f f
7