7.5.6 Protective Functions: L
7-92
D
Timing Chart for Frequency Detection Operation
Related
constant
L4-01: Speed Agree Level
L4-02: Speed Agree Width
L4-03: Speed Agree Level +/
L4-04: Speed Agree Width
Fref/Fout Agree 1 Fref/Fout Agree 2
Fref/Fout
Agree
OFF ON
Frequency
reference
L4-02
L4-02
Output frequency
or motor speed
Fref/Fout Agree 1
(Multi-function output setting = 2)
OFF ON
Frequency
reference
Output frequency
or motor speed
Fref/Fout Agree 2
L4-04
(Multi-function output setting = 13)
Fref/Set Agree 1
(ON at the following conditions during frequency agree)
Fref/Set Agree 2
(ON at the following conditions during frequency agree)
Fref/Set
Agree
OFF ON
Output frequency
or motor speed
Fref/Set Agree 1
L4-02
L4-01
L4-01
L4-02
(Multi-function output setting = 3)
OFF ON
Output frequency
or motor speed
Fref/Set Agree 2
L4-04
L4-03
(Multi-function output setting = 14)
Frequency (FOUT) Detection 1
( L4-01 > | Output frequency | )
Frequency (FOUT) Detection 3
( L4-03 > Output frequency )
Fre
q
uenc
y
Freq. Detection 1
OFFON
Output frequency
or motor speed
L4-02
L4-02
L4-01
L4-01
(Multi-function output setting = 4)
Freq. Detection 3
OFFON
Output frequency
or motor speed
L4-04
L4-03
(Multi-function output setting = 15)
Frequency
Detection
Frequency (FOUT) Detection 2
( L4-01 < | Output frequency | )
Frequency Detection 4
( L4-03 < Output frequency )
Freq. Detection 2
OFF ON
Output frequency
or motor speed
L4-02
L4-02
L4-01
L4-01
(Multi-function output setting = 5)
Freq. Detection 4
OFF ON
Output frequency
or motor speed
L4-04
L4-03
(Multi-function output setting = 16)