4.2 Modes
4-17
Indicates the control methods and access levels under which the constant can be accessed
and set.
V
alid
Access
Q
Accessible/settable under all access levels (Quick-start, Basic, and Advanced).
V
alid
Access
Levels
B
Accessible/settable under Advanced or Basic access levels.
A
Accessible/settable under Advanced access level.
×
Not accessible/settable in the specified control method.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
o1-02
Monitor selection af-
ter power up
f
1to4 1
B B B B
Use constant o1-02 to indicate which value will be displayed when the Inverter is started. Refer to the fol-
lowing table.
Monitor Display Contents at Startup
Setting Contents
1
Indicates the frequency reference at startup.
2
Indicates the output frequency at startup.
3
Indicates the output current at startup.
4
Indicates the value set in user constant o1-01 at startup.
A
EXAMPLE
"
Changing Monitor Display to Output Power at Startup in Basic Access Level
Change the access level to Basic if it is not already set there. Refer to Figure 4.4 for the procedure to change
from the Quick-start to Basic access level.
Use the following procedure to change the display from the output voltage to the output power.
Step Key Sequence Digital Operator Display Remarks
1
MENU
G5: Main Menu :
Operation
2
Press twice.
G5: Main Menu :
Programming
3
DATA
ENTER
Function b1
Sequence
Changed to constant reading (func-
tion) level.
4
Press twice.
Function o1
Monitor Select
5
DATA
ENTER
User Monitor Sel
Output Voltage
Changed to constant setting level.
6
DATA
ENTER
o101 = 6:::
Output Voltage
7
Press twice.
o101 = 8
Output kWatts
8
DATA
ENTER
Entry Accepted
Writes-in the new setting.
User Monitor Sel
Output kWatts
After a few seconds, the Operator dis-
play is as shown on the left.
Output power has been set in place of output voltage.