8.2 Programming Mode Constants
8-31
J
Analog Inputs: H3
Name
Change
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
H3-01
Signal level selection
(terminal 13)
0: 0 to + 10V [11-bit + polarity
(positive/negative) input]
0, 1 0
×
B B B B
6-4
Term 13 Signal
1: 0 to ± 10V
,
Gain (terminal 13)
Sets the frequency when 10 V is
0.0 to
H3-02
Terminal 13 Gain
input, as a percentage of the maxi-
mum output frequency.
.
1000.0
100.0
f
B B B B
6-7
Bias (terminal 13)
Sets the frequency when 0 V is in-
− 100.0
H3-03
Terminal 13 Bias
put, as a percentage of the maxi-
mum frequency.
to
+ 100.0
0.0
f
B B B B
6-7
H3-04
Signal level selection
(terminal 16)
0: 0 to + 10V [11-bit + polarity
(positive/negative) input]
0, 1 0
×
B B B B
6-7
Term 16 Signal
1: 0 to ± 10V
,
H3-05
Multi-function analog
input (terminal 16)
Select from the functions listed in
the followin
table. Refer to
a
e
0to1F 0
×
B B B B
7-79
Terminal 16 Sel
.
7 - 79.
Gain (terminal 16)
Sets the input gain (level) when
terminal 16 is 10 V.
0.0 to
H3-06
Terminal 16 Gain
Set according to the 100% value
on page 7 - 79.
.
1000.0
100.0
f
B B B B
6-7
Bias (terminal 16)
Sets the input gain (level) when
terminal 16 is 0 V.
− 100.0
H3-07
Terminal 16 Bias
Set according to the 100% value
on page 7 - 79
to
+ 100.0
0.0
f
B B B B
6-7
H3-08
Signal level selection
(terminal 14)
0: 0 to +10 V (Always cut jump-
er wire J1)
1: 0 to ±10 V
Alwa
s cut
um
-
0to2 2
×
A A A A
6-4
Term 14 Sel
er wire J1)
2: 4 to 20 mA (10-bit input)
H3-09
Multi-function analog
input (terminal 14)
Set as for H3-05.
:Cannot be set to 0. The 1F func-
1to1F 1F
×
A A A A
7-79
Terminal 14 Sel
tion will become “frequency
reference.”
Gain (terminal 14)
Sets the input gain (level) when
terminal 14 is 10 V (20 mA).
Set accordin
to the 100% value
0.0 to
H3-10
Terminal 14 Gain
on page 7 - 79.
If H3-09 = “1F” the setting in
H3-02 is used.
.
1000.0
100.0
f
A A A A
6-7
Bias (terminal 14)
Sets the input gain (level) when
terminal 14 is 0 V (4 mA).
Set accordin
to the 100% value
− 100.0
H3-11
Terminal 14 Bias
on page 7 - 79.
If H3-09 = “1F” the setting in
H3-03 is used.
to
+ 100.0
0.0
f
A A A A
6-7
H3-12
Analog input filter
time constant
Sets terminals 13, 14, 16 to prima-
ry delay filter time constant, in se-
0.00 to
0.00
×
A A A A
6-7
Filter Avg Time
con
sun
s.
:Effective for noise control etc.
2.00
.
8