3.7 Installing and Wiring PG Speed Control Cards
3-25
3.7.2 PG Speed Control Card Terminal Blocks
The terminal specifications for each PG Speed Control Card are given in the following tables.
J
PG-A2 (For V/f with PG Feedback Mode Only)
Table 3.10 PG-A2 Terminal Specifications
Terminal No. Contents Specifications
1
12 VDC (±5%), 200 mA max.
2
Power supply for pulse generator
0 VDC (GND for power supply)
3
+12 V/o
en collector switching ter-
Terminal for switching between12 V voltage input
4
minal
and open collector input. For open collector input,
short across 3 and 4.
TA1
5
Pulse in
ut terminal
H: +4 to 12 V; L: +1 V max. (Maximum response
frequency: 30 kHz)
6
Pulse input common
7
12 VDC (+10%), 20 mA max.
8
Pulse motor output terminal
Pulse monitor output common
TA2 (E)
Shield connection terminal
J
PG-B2 (For Flux Vector Control Mode Only)
Table 3.11 PG-B2 Terminal Specifications
Terminal No. Contents Specifications
1
12 VDC (±5%), 200 mA max.
2
Power supply for pulse generator
0 VDC (GND for power supply)
3
A-phase pulse input terminal
H: +8to12V
L: +1 V max.
(Maximum response frequency: 30 kHz)
TA1
4
Pulse input common
5
B-phase pulse input terminal
H: +8to12V
L: +1 V max.
(Maximum response frequency: 30 kHz)
6
Pulse input common
1
Open collector output, 24 VDC, 30 mA max.
2
A-phase monitor output terminal
A-phase monitor output common
TA2
3
Open collector output, 24 VDC, 30 mA max.
4
B-phase monitor output terminal
B-phase monitor output common
TA3 (E)
Shield connection terminal
J
PG-D2 (For V/f with PG Feedback Mode Only)
Table 3.12 PG-D2 Terminal Specifications
Terminal No. Contents Specifications
1
12 VDC (±5%), 200 mA max. (see note)
2
Power supply for pulse generator
0 VDC (GND for power supply)
3
5 VDC (±5%), 200 mA max. (see note)
4
Pulse input + terminal
Line driver in
ut
RS-422 level in
ut
TA1
5
Pulse input − terminal
Maximum response frequency: 300 kHz
6
Common terminal
7
Pulse monitor output + terminal
8
Pulse monitor output − terminal
Line driver output (RS-422 level output)
TA2 (E)
Shield connection terminal
Note 5 VDC and 12 VDC cannot be used at the same time.
3