7.5.7 Operator Constants: o
7-98
Frequency Units of Constant Setting: o1-04
D This constant can be used to change the setting unit for Flux vector control constants to r/min.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
o1-04
Frequency units of
constant setting
×
0, 1 0
× × ×
B
D Settings
Setting Unit
0
Unit of setting: Hz
1
Unit of setting: r/min
Constant Number Display Selection: o1-05
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
o1-05
Constant No. display
selection
×
0, 1 0
A A A A
D
Settings
Setting Function
0
Display constant number
1
Display constant number (address) set for MEMOBUS communications
J Key Function Settings/Other Settings: o2-01 to o2-08
LOCAL/REMOTE Key Enable/Disable: o2-01
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
o2-01
LOCAL/REMOTE
key enable/disable
×
0, 1 1
B B B B
D
This constant enables or disables the LOCAL/REMOTE Key (the Operation Mode Selector Key) on
the Digital Operator.
D
Settings
Setting Function
0
Disabled. (Cannot change between local and remote.)
1
Enabled. (Pressing the LOCAL/REMOTE Key switches control of operation between the Oper-
ator and the sources specified in constants b1-01 and b1-02.)
STOP Key During Control Circuit Terminal Operation: o2-02
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
o2-02
STOP Key during
control circuit termi-
nal operation
×
0, 1 1
B B B B
D
This constant enables or disables the STOP on the Digital Operator
D
Settings
Setting Function
0
Disabled. (The STOP Key is disabled when the run command is input from an external termi-
nal.)
1
Enabled. (The STOP Key is enabled at all times during operation.)
7