EasyManua.ls Logo

YASKAWA CIPR-GA50CB001

YASKAWA CIPR-GA50CB001
79 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 Attachment
YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction 307
Model Terminal
Recommen
ded Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Wire
Stripping
Length
*1
mm
Terminal Screw
Tightening
Torque
Nm (inlb)
Size Shape
4044
R/L1, S/L2, T/L3 4 10 - 2 18 M5
AWG 10
2.3 - 2.5
(19.8 - 22)
AWG 8
4.1 - 4.5
(36 - 40)
U/T1, V/T2, W/T3 6 12 - 4 18 M5
AWG 10
2.3 - 2.5
(19.8 - 22)
AWG 8
4.1 - 4.5
(36 - 40)
-, +1, +2 2 8 - 2 18 M5
4.1 - 4.5
(36 - 40)
B1, B2 8 12 - 6 10 M4
1.5 - 1.7
(13.5 - 15)
6 10 - 6 - M6
5.4 - 6.0
(47.8 - 53.1)
4060
R/L1, S/L2, T/L3 2 8 - 2 18 M5
4.1 - 4.5
(36 - 40)
U/T1, V/T2, W/T3 4 10 - 2 18 M5
AWG 10
2.3 - 2.5
(19.8 - 22)
AWG 8
4.1 - 4.5
(36 - 40)
-, +1, +2 2 6 - 2 18 M5
4.1 - 4.5
(36 - 40)
B1, B2 8 12 - 6 10 M4
1.5 - 1.7
(13.5 - 15)
6 10 - 6 - M6
5.4 - 6.0
(47.8 - 53.1)
*1 Remove insulation from the ends of wires to expose the length of wire shown.
*2 If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-
loop crimp terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of
10 mm
2
(copper wire).
8-4NS from JST Mfg. Co., Ltd.
R8-4S from NICHIFU Co.,Ltd.

Table of Contents

Other manuals for YASKAWA CIPR-GA50CB001

Related product manuals