EasyManuals Logo
Home>YASKAWA>DC Drives>FP65U T Series

YASKAWA FP65U T Series User Manual

YASKAWA FP65U T Series
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
7 Electrical Installation
34 YASKAWA TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
Model Terminals
Recommended
Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
(mm
2
)
*1
IP20 Applicable Gauge
*2
AWG, kcmil
(mm
2
)
*1
Wire Stripping
Length
*3
mm
Terminal Screw
Size and Shape
Tightening Torque
Nm (lbfin)
2143
R/L1, S/L2, T/L3 2/0
6 - 4/0
(16 - 95)
- -
M8
13.5 - 15
(119.5 - 132.8)
U/T1, V/T2, W/T3 3/0
6 - 4/0
(16 - 95)
- -
M8
13.5 - 15
(119.5 - 132.8)
-, +1 3/0
6 - 4/0
(16 - 95)
- -
M8
13.5 - 15
(119.5 - 132.8)
4
6 - 4/0
(16 - 95)
- -
M8
9.0 - 11
(79.7 - 97.4)
2169
R/L1, S/L2, T/L3 3/0
6 - 4/0
(16 - 95)
- -
M8
13.5 - 15
(119.5 - 132.8)
U/T1, V/T2, W/T3 4/0
6 - 4/0
(16 - 95)
- -
M8
13.5 - 15
(119.5 - 132.8)
-, +1 1/0 × 2
6 - 4/0
(16 - 95)
- -
M8
13.5 - 15
(119.5 - 132.8)
4
6 - 4/0
(16 - 95)
- -
M8
9.0 - 11
(79.7 - 97.4)
2211
R/L1, S/L2, T/L3 1/0 × 2
3 - 4/0 × 2P
(25 - 95 × 2P)
2/0 - 4/0 × 2P
(70 - 95 × 2P)
-
M10
18 - 20
(159.3 - 177)
U/T1, V/T2, W/T3 1/0 × 2
3 - 4/0 × 2P
(25 - 95 × 2P)
2/0 - 4/0 × 2P
(70 - 95 × 2P)
-
M10
18 - 20
(159.3 - 177)
-, +1 2/0 × 2
2 - 250 × 2P
(35 - 120 × 2P)
4/0 - 250 × 2P
(95 - 120 × 2P)
-
M10
18 - 20
(159.3 - 177)
3 or 2
4 - 350
(25 - 185)
- -
M10
18 - 23
(159 - 204)
2273
R/L1, S/L2, T/L3 2/0 × 2
3 - 4/0 × 2P
(25 - 95 × 2P)
2/0 - 4/0 × 2P
(70 - 95 × 2P)
-
M10
18 - 20
(159.3 - 177)
U/T1, V/T2, W/T3 2/0 × 2
3 - 4/0 × 2P
(25 - 95 × 2P)
2/0 - 4/0 × 2P
(70 - 95 × 2P)
-
M10
18 - 20
(159.3 - 177)
-, +1 4/0 × 2
2 - 250 × 2P
(35 - 120 × 2P)
4/0 - 250 × 2P
(95 - 120 × 2P)
-
M10
18 - 20
(159.3 - 177)
2
4 - 350
(25 - 185)
- -
M10
18 - 23
(159 - 204)
2343
R/L1, S/L2, T/L3 4/0 × 2
2/0 - 300 × 2P
(70 - 150 × 2P)
250 - 300 × 2P
(120 - 150 × 2P)
-
M12
31.5 - 35
(279 - 310)
U/T1, V/T2, W/T3 4/0 × 2
2/0 - 300 × 2P
(70 - 150 × 2P)
250 - 300 × 2P
(120 - 150 × 2P)
-
M12
31.5 - 35
(279 - 310)
-, +1 250 × 2
4/0 - 400 × 2P
(95 - 185 × 2P)
300 - 400 × 2P
(150 - 185 × 2P)
-
M12
31.5 - 35
(279 - 310)
1/0
1 - 350
(50 - 185)
- -
M12
32 - 40
(283 - 354)
2396
R/L1, S/L2, T/L3 250 × 2
2/0 - 300 × 2P
(70 - 150 × 2P)
250 - 300 × 2P
(120 - 150 × 2P)
-
M12
31.5 - 35
(279 - 310)
U/T1, V/T2, W/T3 250 × 2
2/0 - 300 × 2P
(70 - 150 × 2P)
250 - 300 × 2P
(120 - 150 × 2P)
-
M12
31.5 - 35
(279 - 310)
-, +1 350 × 2
4/0 - 400 × 2P
(95 - 185 × 2P)
300 - 400 × 2P
(150 - 185 × 2P)
-
M12
31.5 - 35
(279 - 310)
1/0
1 - 350
(50 - 185)
- -
M12
32 - 40
(283 - 354)
*1 The metric wire gauge values are provided as reference information from equivalent AWG sizes and not exactly the same sizes as the
AWG/kcmil values. Obey local safety regulations for wire sizes and make sure that the ferrule or crimp terminals are correct for your size.
*2 For IP20 protection, use wires that are in the range of applicable gauges.
*3 Remove insulation from the ends of wires to expose the length of wire shown.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA FP65U T Series and is the answer not in the manual?

YASKAWA FP65U T Series Specifications

General IconGeneral
BrandYASKAWA
ModelFP65U T Series
CategoryDC Drives
LanguageEnglish