12 Drive Control, Duty Modes, and Programming
86 YASKAWA TOEPC71061752B GA500 Drive Installation & Primary Operation
No.
(Hex.)
Name Description
d1-01 - d1-16
(0280 - 0291)
RUN
Reference 1 to 16
Sets the frequency reference in the units from o1-03 [Frequency Display Unit
Selection.
d1-17
(0292)
RUN
Jog Reference
Sets the Jog frequency reference in the units from o1-03 [Frequency Display
Unit Selection]. Set H1-xx = 6 [MFDI Function Select = Jog Reference
Selection] to use the Jog frequency reference.
d2-01
(0289)
Frequency Reference
Upper Limit
Sets maximum limit for all frequency references. The maximum output
frequency is 100%.
d2-02
(028A)
Frequency Reference
Lower Limit
Sets minimum limit for all frequency references. The maximum output
frequency is 100%.
E1-01
(0300)
Input AC Supply
Voltage
Sets the drive input voltage.
E1-04
(0303)
Maximum Output
Frequency
Sets the maximum output frequency for the V/f pattern.
E1-05
(0304)
Maximum Output
Voltage
Sets the maximum output voltage for the V/f pattern.
E1-06
(0305)
Base Frequency
Sets the base frequency for the V/f pattern.
E1-09
(0308)
Minimum Output
Frequency
Sets the minimum output frequency for the V/f pattern.
E2-01
(030E)
Motor Rated Current
(FLA)
Sets the motor rated current in amps.
E2-11
(0318)
Motor Rated Power
Sets the motor rated output in the units from o1-58 [Motor Power Unit
Selection].
H1-01 - H1-
07
(0438, 0439,
0400 - 0404)
Terminal S1 to S7
Function Selection
Sets the function for MFDO terminals S1 to S7.
H2-01
(040B)
Term MA/MB-MC
Function Selection
Sets the function set for MFDO terminal MA-MC or MB-MC.
H2-02
(040C)
Term P1-C1 Function
Selection
Sets the function for MFDO terminal P1-C1.
H2-03
(040D)
Term P2-C2 Function
Selection
Sets the function for MFDO terminal P2-C2.
H3-01
(0410)
Terminal A1 Signal
Level Select
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
4 : -10 to +10V (Bipolar Reference)