CPF21
Option CPU down
The CPU on the SI-B option board has locked up.
N/A
CPF22
Option Type Err
DPRAM fault detected at power up.
N/A
Possible Cause(s): Noise or spike on the communication line, defective SI-B option board.
Corrective Action: Perform a factory initialization , cycle power, replace the option board,
replace the control board.
Possible Cause(s): Unrecognizable communication or network option board is connected to
the control board.
Corrective Action: Remove any option boards and cycle power, perform a factory initialization,
replace the option board, replace the control board.
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
505