Both the forward and the reverse run commands are
input simultaneously for 500 ms or more.
EF
External Fault
ef
Possible Cause(s): An external forward and reverse command are input simultaneously.
Corrective Action: Check external sequence logic.
ef0
External fault from serial communication.
Possible Cause(s): An external fault condition exists.
Corrective Action: Check for an external condition, verify the program parameters.
EF0
External Fault
F
ault Codes
Minor Fault - Operation continues and the digital operator indication blinks
The fault relay does not activate.