PP.P5G5.03.Troubleshoot
Page 38
Rev. 06/11/2003
Fault Codes
Parameter Setting Error - Inverter can’t run. The fault is displayed
on the digital operator, and the fault relay is not activated.
OPE11
FC/ On-Dly
Carrier frequency data setting fault.
Upper limit (C6-01) >5KHz, and the lower limit
(C6-02) <= 5KHz.
Carrier frequency proportional gain (C6-03) > 6 and
(C6-01) < (C6-02).
N/A
Possible Cause(s): Parameter setting incorrect.
Corrective Action: Check the program settings and correct the errors.
Possible Cause(s): Connection not made properly, user software not configured to the
proper baud rate or configuration.
Corrective Action: Check all connections, verify all user side software configurations.
CALL
Serial Com Call
Serial communication transmission error.
Communication has not yet been established.
call
505
506 515
505
506 515