EasyManua.ls Logo

YASKAWA L1000E - Page 222

YASKAWA L1000E
236 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
C Standards Compliance
222 YASK AWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum
allowable temperature of 75°C 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed 40°C.
Table 57 Wire Gauge and Torque Specifications (Three-Phase 400 V Class)
2A0269
R/L1, S/L2, T/L3
95 × 2P
(3/0 × 2P)
95 to 150
(3/0 to 300)
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
95 × 2P
(3/0 × 2P)
95 to 150
(3/0 to 300)
–, +1
95 to 150
(3/0 to 300)
+3
35 to 150
(2 to 300)
M10
18 to 23
(159 to 204)
35
(3)
35 to 150
(2 to 300)
M12
32 to 40
(283 to 354)
2A0354
R/L1, S/L2, T/L3
120 × 2P
(4/0 × 2P)
95 to 150
(3/0 to 300)
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
120 × 2P
(4/0 × 2P)
95 to 150
(3/0 to 300)
–, +1
95 to 150
(3/0 to 300)
+3
95 to 150
(3/0 to 300)
M10
18 to 23
(159 to 204)
35
(2)
35 to 150
(2 to 300)
M12
32 to 40
(283 to 354)
2A0432
R/L1, S/L2, T/L3
150 × 2P
(250 × 2P)
95 to 300
(4/0 to 600)
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
185 × 2P
(300 × 2P)
95 to 300
(4/0 to 600)
–, +1
120 to 300
(250 to 600)
+3
70 to 300
(3/0 to 600)
M10
18 to 23
(159 to 204)
50
(1)
120 to 240
(1 to 350)
M12
32 to 40
(283 to 354)
Drive Model Terminal
Recommended
Wire Size
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Screw
Size
Tightening Torque
N•m (lb.in.)
4A0009
R/L1, S/L2, T/L3
2.5
(14)
2.5 to 6.0
(14 to 10)
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
2.5
(14)
2.5 to 6.0
(14 to 10)
–, +1, +2
2.5 to 6.0
(14 to 10)
B1, B2
2.5 to 6.0
(14 to 10)
6.0
(10)
2.5 to 6.0
(14 to 10)
Drive Model Terminal
Recommended
Wire Size
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Screw
Size
Tightening Torque
N•m (lb.in.)

Related product manuals