YASKAWA TOEPYAIUPW02A U1000 iQpump Drive Quick Start Procedure
U1000 iQpump Drive
Quick Start Procedure
Page 14
of 25
Fine-tune Settings for Pumping Application
8
STEP
0: No Unit 8:
o
F: DegFarenheit
1: PSI: lb.SqrInch
9:
o
C: DegCelsius
2: Pa: Pascals
10: %: Percent
11: kPA: kilopascal
25: Flow (Use P6-04)
26: Custom Units
3: Bar
4: WC: Inch Water
5: “Hg: Inch Mercury
6: ft: Feet
7: m: meters
Feedback
Maximum
Start Pump System
Start
Delay
200
PSI
Start / Draw Down Level (P1-04)
(Example 100.0 PSI)
System Setpoint
(Example 150.0 PSI)
Feedback Signal from pressure
transducer (4 – 20 mA)
0
Time
Pressure
Start Level Delay (P1-05)
(Example 5.0 seconds)
System Units (P1-02)
(Example PSI P1-02=1)
Feedback Scaling (P1-03)
(Example 200.0 PSI)
WAIT
SYSTEM STARTS WHEN
PRESSURE SIGNAL FALLS
BELOW 100 PSI
Example: Absolute Level (Positive Start Level) P1-02 Feedback Unit Example: Absolute Level (Negative Start Level)
150
Start Pump System
Start
Delay
Start / Draw Down Level (P1-04)
(Example -50.0 PSI, (150.0 – 50.0)
System Setpoint
(Example 150.0 PSI)
Feedback Signal from pressure
transducer (4 – 20 mA)
Time
Pressure
Start Level Delay (P1-05)
(Example 5.0 seconds)
System Units (P1-02)
Feedback Scaling (P1-03)
(Example 200.0 PSI)
WAIT
SYSTEM STARTS WHEN
PRESSURE SIGNAL FALLS
BELOW 100 PSI
-50.0 PSI
150
200
PSI
P1-03 200.0 Feedback Scaling
(Example PSI P1-02=1)
8.1 System Feedback Unit/
Feedback Device Scaling
8.2 Start/Draw Down Level - Positive Start 8.3 Start/Draw Down Level - Negative Start
8.4 Sleep Mode (Example)
Minimum Speed P1-06
(Example 40.0 Hz)
Output Frequency
(
pump motor speed
)
0
Sleep Delay Time (P2-03)
(Example 5.0 seconds)
Ramp or Coast to Stop, b1-03
Output Frequency
60 Hz
Pump Running
Go to Sleep
Time
WAIT FOR PRESSURE TO FALL BELOW
START/DRAW DOWN LEVEL (P1-04)
System goes to sleep when pump
Motor speed drops to 40 Hz.
(2400 RPM for 3600 RPM motor)
8.5 Pump System Fault Setup
FEEDBACK SIGNAL
Time
SETPOINT
SET-POINT NOT MET
P1-16
Setpoint-LOP Time
The drive will display a “Setpoint Not Met” fault when the drive is unable to maintain the
programmed system setpoint due a problem with the pump system.Set P1-15 to the maximum allowed difference
between setpoint and feedback level.
P1-15 Maximum Setpoint Diff
8.6 Low/High Feedback Level Detection
The drive continuously monitors the system feedback signal. Set the low feedback level parameter P1-08 to the minimum feedback level
allowed for your system to display a “Low Feedback” fault. Set the high feedback level parameter P1-11 to the maximum feedback level
allowed to display a “High Feedback” fault.