Verify Pump Rotation and Transducer Feedback (continued)
9
STEP
9.3 Exchange Output Leads
De-energize the drive and wait at least ve minutes until the charge indicator extinguishes completely before touching any wiring,
circuit boards or components. Failure to comply may result in electrocution.
Exchange Output Leads
HOA keypad
(drive de-energized)
Swap any two of the
three output leads to the motor
(U/T1, V/T2 and W/T3) to change
the motor rotation direction.
Refer to Figure 3.1.
Repeat Step 9 to confirm the direction
of motor rotation.
9.4 Feedback Signal Check
Verify Feedback on Display
Refer to parameter P1-02 and P1-03, if the
feedback device scaling or system units are
incorrect.
Verify feedback on display matches the mechanical pressure gauge.
Feedback Signal Level
U1-02= 0.00Hz
U5-99= 0.0
PSI
Auto Setpoint
- MODE - DRV Rdy
U1-91= 56.2PSI
MONITOR
LSEQ
LREF
AUTO Mode Operation
10
STEP
Perform these tasks to operate the drive in AUTO mode:
Program all parameters
Verify motor rotation direction
AUTO Mode: Select the frequency reference source setting in parameter b1-01 (Refer to Step 4.6 for an example of
setting a parameter.)
b1-01 = 0 is the default setting (Operator/HOA Keypad)
AUTO Mode: Select the run command source setting in parameter b1-02 (Refer to Step 4.6 for an example of
setting a parameter.)
b1-02 = 0 is the default setting (Operator/HOA Keypad)