2 INSTALLATION
D
Lift the cabinet by the base. When moving the unit, never lift by the front
cover or the front panel.
Otherwise, the main unit may be dropped causing damage to the unit.
D
Mount the power regenerative unit on nonflammable material (i.e. metal).
Failure to observe this caution can result in a fire.
D
When mounting units in an enclosure, install a fan or other cooling device
to keep the intake air temperature below 45°C.
Overheating may cause a fire or damage to the unit.
This chapter describes the configuration, location and space when mounting the
VS-656RC5.
2.1 CHECKING INSTALLATION SITE
(1) Installation Site
Install the power regenerative unit under the following conditions.
Type Ambient Operating Temperature Humidity
Enclosed
wall-mounted
−10 to + 40 °C 90 % RH or less (no condensation)
Open chassis
−10 to + 45 °C 90 % RH or less (no condensation)
Protection covers are attached to the top and bottom of the power regenerative
unit. Be sure to remove the protection covers before installing a 200 or 400 V
Class power regenerative unit with an output of 30 kW or less in a panel.
CAUTION