IM 12A01A02-01E 4/11
8th Edition
(page 1-10) change
l FLXA202 and FLXA21
Intrinsic safety and nonincendive (sufx code Type : -CB, -CD, -DD, -CH):
ATEX Intrinsic safety approval
Applicable standard
Explosive Atmospheres
EN 60079-0:2012/A11: 2013 Equipment - General requirements
EN 60079-11:2012 Equipment protection by Intrinsic safety “i”
EN 60079-26:2007 Equipment with equipment protection level (EPL) Ga
EN 60529:1992 Degrees of protection provided by enclosures (IP Code)
Type of protection
II 1 G Ex ia IIC T4 Ga
Group: II
Category: 1 G
T4: for ambient temperature:–20 to 55ºC
Atmosphere pressure: 80kPa (0.8bar) to 110kPa (1.1bar)
Degree of Protection of the Enclosure: IP66
IECEx Intrinsic safety approval
Applicable standard
IEC 60079-0:2011 Part 0: Equipment - General requirements
IEC 60079-11: 2011 Part 11: Equipment protection by intrinsic safety “i”
IEC 60079-26: 2006 Part 26: Equipment with equipment protection level (EPL) Ga
IEC 60529: 2001 Degrees of protection provided by enclosures (IP Code)
Type of protection
Ex ia IIC T4 Ga
T4: for ambient temperature:–20 to 55ºC
Atmosphere pressure: 80 kPa (0.8 bar) to 110 kPa (1.1 bar)
Degree of Protection of the Enclosure: IP66
(page 1-11) addition
FM Intrinsic safety and nonincendive approval
Applicable standard
Class-3600: 2011 Approval Standard for Electric Equipment for use in Hazardous (Classied)
Locations General Requirement
Class-3610: 2010 Approval Standard for Intrinsically Safe Apparatus and Associated Apparatus for
Use in Class I, II, and III, Division 1, Hazardous (Classied) Locations
Class-3611: 2004 Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class
III, Divisions 1 and 2, Hazardous (Classied) Locations
Class-3810: 2005 Electrical Equipment for Measurement, Control and Laboratory Use
ANSI/NEMA 250:2014 Enclosures for Electrical Equipment (1000 Volts Maximum)
ANSI/ISA 60079-0 2013 Part 0: General Requirements
ANSI/ISA 60079-11 2014 Part 11: Equipment protection by intrinsic safety “i”
Type of protection
Class I, Division 1, Groups A, B, C and D (Intrinsically Safe)
Class I, Division 2, Groups A, B, C and D (Nonincendive)
Class I, Zone 0, Group IIC, in Hazardous (Classied) Locations (Intrinsically Safe AEx ia IIC)
Class I, Zone 2, Group IIC, in Hazardous (Classied) Locations (Nonincendive)
For all protection type, T4: for ambient temperature: -20 to 55°C
Atmosphere pressure: 80 kPa (0.8 bar) to 110 kPa (1.1 bar)
CSA Intrinsic safety and nonincendive approval
Applicable standard
C22.2 No. 0-10 (R2015) General Requirements - Canadian Electrical Code Part II
CAN/CSA C22.2 No. 94-M91 (R2011) Special Purpose Enclosures
C22.2 No213-M1987 (R2013) Nonincendive Electrical Equipment for Use in Class I, Division 2
Hazardous Locations
CAN/CSA C22.2 No.60079-0:11 Electrical apparatus for explosive gas atmospheres - Part 0:
General requirements
CAN/CSA C22.2 No.60079-11:14 Electrical apparatus for explosive gas atmospheres - Part 11:
Intrinsic safety “i”
Type of protection
Class I, Division 1, Groups A, B, C and D
Ex ia IIC T4 Ga (Intrinsically Safe)
Class I, Division 2, Groups A, B, C and D (Nonincendive)
For all protection type, T4: for ambient temperature: -20 to 55°C
Atmosphere pressure: 80 kPa (0.8 bar) to 110 kPa (1.1 bar)
Ambient Humidity: 0 to 100% (No condensation)