<APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF RAMC>
A-6
All Rights Reserved. Copyright © 2006, Rota Yokogawa
IM 01R01B02-01E-E 5th edition October 01, 2020-00
Abs.
Index
Parameter Sub-
Parameter
Label Data Type/
Structure
Read/
Write
Initial value Functional Description
48 LO_ALM - DS-39 R/- -
State of the lower warning limit
Unacknowledged Lower Unack.
Warnings
Unsigned8 R/- 0 For future use (not available)
Alarm_State Lower Warning
Status
Unsigned8 R/- 0: No Warning Indicates the warning status
Time Stamp - Time Value R/- 0 For future use (not available)
Subcode - Unsigned16 R/- 0 For future use (not available)
Value Lower Warning
Output Value
Float R/- 0 Indicates the value which caused the
warning
49 LO_LO_ALM - DS-39 R/- - State of the lower alarm limit
Unacknowledged Lower Unack.
Alarms
Unsigned8 R/- 0 For future use (not available)
Alarm_State Lower Alarm
Status
Unsigned8 R/- 0: No Alarm Indicates the alarm status
Time Stamp - Time Value R/- 0 For future use (not available)
Subcode - Unsigned16 R/- 0 For future use (not available)
Value Lower Alarm
Output Value
Float R/- 0 Indicates the value which caused the
alarm
50 SIMULATE - DS-50 R/- - Simulation of Transducer Block input
into the Analog Input Function Block
Simulate_Status Simulation Status Unsigned8 R/- - Indication and input of simulation value
Simulate_Value Simulation Value Float R/- 0.0 Indication and input of simulation status
Simulate_Enabled Simulation Unsigned8 R/- 0: Disabled Enables and disables simulation (inter-
rupts transducer block input)
51 OUT_UNIT_TEXT Out unit text Octet String R/- - Indication and input of customer specic
textual unit of OUT parameter (used for
units not contained in the code list).
230 VIEW_1 - R/- n.a. Indicates a Prole dened parameter
preselection
231 VIEW_2 - R/- n.a. Indicates a Prole dened parameter
preselection