EasyManuals Logo

YOKOGAWA UT52A User Manual

YOKOGAWA UT52A
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #8 background imageLoading...
Page #8 background image
IM 05P01C31-15EN page 8/12
7.
Switching between REM (Remote) and LCL (Local)
Remoteandlocalswitchingcanbeperformedusinganyofthefollowing:
(1)Contactinput,(2)Parameter,(3)Communication,and(4)Userfunctionkey.
LCL (Local)
Controlisperformedusingthetargetsetpointsetonthecontroller.
REM (Remote)
Controlisperformedusinganexternalanalogsignalthatisusedasthetargetset-
point.Thefollowingshowsan exampleofswitchingfromlocalto remoteusingthe
parameter.
Fordetailsofotherswitchingmethods,seeUser’sManual(IM05P01C31-01EN).
•ThePIDgroupforthelocalSPnumberisusedasPIDinremotemode.
NOTE
WhenthecontactinputisON,operationcannotbeperformedusingtheparameter,
communication,orkey. Whenthecontactinput isOFFandthe settingisswitched
usingtheparameter,communication,orkey, thelastswitchingoperationis per-
formed.
Show the Operation Display.
Hold down the PARAMETER key or PARA key
for 3 seconds to display MODE menu.
Press the SET/ENTER key.
1.
2.
Press the SET/ENTER key.
The REM lamp is lit.
Change the operation mode using
the Up/Down arrow keys.
Blinks during the change.
Press the SET/ENTER key.
3.
4.
5.
The parameter R.L (REMOTE/LOCAL switch)
is displayed.
8.
Manipulating Control Output in Manual Mode
NOTE
Inmanualmode,controloutput ismanipulatedbyoperatingthekeys (thevalueis
changedusingtheUp/Downarrowkeys,thenoutputtedasitis).
EveniftheSET/ENTER keyisnotpressed, thecontroloutputvalue changesac-
cordingtothedisplayedvalue.
Instopmode(whentheSTOPlampislit),controloutputcannotbemanipulated.
MAN lamp is lit.
Up arrow key: increases control output.
Down arrow key: decreases control output.
In Position proportional control:
Up arrow key; opens the valve.
Down arrow key; closes the valve.
Output; only while pressing a key.
OUT; valve opening (0-100%)
Output manipulation in Position proportional control
is not restricted from output limiters (OH, OL).
Manual operation in Heating/cooling control
Symbol of cooling side
Target setpoint (SP) number
Symbol of heating side
Heating-side control output
Cooling-side control output
Uparrowkey:concurrently decreasescooling-sidecontroloutput andincreases
heating-sidecontroloutput.
Downarrowkey:concurrentlyincreasescooling-sidecontroloutput anddecreases
heating-sidecontroloutput.
(Eithernoneoftheheating-sideand cooling-sideoutputsarepresented,orboth of
themarepresentedaccordingtothedeadbandsetting.)
Actual output (%)
DB=24.8
Dead band: Operation parameter DB
Control computation output Control computation output
12.40-12.4
Manipulated output change
when a dead band is positive (+)
Actual output (%)
100
DB= -24.8
12.40-12.4
Manipulated output change
when a dead band is negative (-)
100
Cooling-side
manipulated output
Heating-side
manipulated output
Heating-side
manipulated output
Cooling-side
manipulated output
9. Troubleshooting
■TroubleshootingFlow
IftheOperationDisplaydoesnotappearafterturningonthecontroller’spower,checktheproceduresinthefollowingowchart.
Ifaproblemappearstobecomplicated,contactoursalesrepresentatives.
Is the controller
defective?
Contact us for repair.
Problem solved.
No communication
capability
Completely
inactive?
Yes
Yes
Yes
No
No
No
Key
operation
failure?
Yes
No
Yes
Check wiring of the
power terminals.
Check the key lock
setting.
Display
failure?
*
Yes
No
Turn off power, and
then turn it on again.
I/O signal
failure?
Yes
No
Check the
supply voltage.
Check the
specifications and polarity
of connected devices .
Check the communication-
related parameters.
Check the specifications
of communication
devices.
Check the
communication wiring.
Communication
failure?
No
With
communi-
cation?
Yes
Yes
Normal?
Is the
key locked?
Check the specifications
of the controller.
Yes
No
Correct?
Correct the error(s).
Cancel the setting.
Check the I/O specifications
of the controller.
* The LCD (a liquid crystal display) is used for
a display portion of this product.
The LCD has a characteristic that the display action
becomes late at the low temperature.
Additionally, the luminance and contrast degradation
are caused due to aged deterioration.
However, the control function is not affected.
■
Remedies if Power Failure Occurs
during Operations
• Instantaneouspowerfailurewithin20ms.
Apowerfailureisnotdetected. Normal
operation continues.
• Powerfailureforlessthanabout5seconds,
orforabout5secondsormore.
Affectsthe"settings"and"operationsta-
tus."
Fordetails,seeUser's Manual(IM
05P01C31-01EN).
NOTE
Writedownthesettingsof parametersfora
repairrequest.
n
Errors at Power On
Theerrorsshownbelowmayoccurinthefaultdiagnosiswhenthepoweristurnedon.(FordetailsofSetpointdisplayandinput/outputactionwheneacherroroccurs,seeUser’sManual(IM05P01C31-01EN).
PV display
(Operation
Display)
Setpoint display
(Operation Display)
Status indicator
(Operation Display)
Parameter that displays error
details
Error description Cause and diagnosis Remedy
Indication off Indication off FaultyMCURAM/MCUROM MCURAM/MCUROMarefailed. Faulty.Contactusforrepair.
ERR
SYS-----
System data error System data is corrupted. Faulty.Contactusforrepair.
PAR0004
(foruserdefaultvalueerroronly)
Setupparameter(PA.ER)
User(parameter)defaultvalueerror
Userparameteriscorrupted.
Initializedtofactorydefaultvalue.
Checkandreconguretheinitialized
settingparameters.Errorindicationis
erased when the power is turned on
again.
PAR0010
(forsetupparametererroronly)
Setup parameter error
Setup parameter data is corrupted.
Initializedtouserdefaultvalue.
PAR0020
(foroperationparametererror
only)
Operationparametererror
Operationparameterdataiscorrupted.
Initializedtouserdefaultvalue.
SLOT0017
(0017:Erroroccurstoall
hardwareofE1toE4-terminal
areas.)
Setupparameter(OP.ER)
Nonrespondinghardwareof
extendedfunction(E1toE4-
terminalareas)
Inconsistence of system data and
hardwareofextendedfunction.
Nonrespondingcommunicationbetween
hardwareofextendedfunction(E1toE4-
terminalareas).
Faulty.
Contactusforrepair.
Normal
indication
Normalindication
Rightmostdecimalpoint
onPVdisplayblinks.
Setupparameter(PA.ER)
Calibrationvalueerror
Initializedtocalibrateddefaultvaluebecause
ofcorruptedfactorydefaultvalue.
Faulty.Contactusforrepair.
Rightmostdecimalpoint
onSymboldisplayblinks.
FaultyFRAM
Datawriting(storing)toFRAMis
impossible.
Normal
indication
Normalindication LADDERlampblinks Setupparameter(LA.ER) Corruptedladderprogram
Ladderprogramiscorrupted.
Operateswithoutladderprogram.
Downloadtheladderprogramagain.
Normal
indication
0.00000000
(Decimalpointontheleftof
theSymboldisplayblinks)
Setupparameter(OP.ER) Userproleerror Userproleiscorrupted. Downloadtheuserproleagain.
n
Errors during Operation
Theerrorsshownbelowmayoccurduringoperation.(Forinput/outputactionwheneacherroroccurs,seeUser’sManual(IM05P01C31-01EN).
PV display
(Operation
Display)
Setpoint display
(Operation Display)
Status indicator
(Operation Display)
Parameter that displays
error details
Error description Cause and diagnosis Remedy
AD.ERR
Normalindication(Note) Setupparameter(AD1.E)
AnaloginputterminalADCerror
•PVinput
•RSPinput(E1-terminalarea)
•AIN2input(E2-terminalarea)
•AIN4input(E4-terminalarea)
AnaloginputterminalADvalueerror
Faulty.
Contactusforrepair.
RJC.E
(DisplaysRJC.
EandPV
alternately.)
Normalindication(Note) Setupparameter(AD1.E)
UniversalinputterminalRJCerror
•PVinput
•RSPinput(E1-terminalarea)
UniversalinputterminalRJCerror
Faulty.
Contactusforrepair.
SettheparameterRJCtoOFFtoerase
error indication.
B.OUT
Normalindication(Note)
Setupparameter(AD1.E)
Analoginputterminalburnouterror
•PVinput
•RSPinput(E1-terminalarea)
•AIN2input(E2-terminalarea)
•AIN4input(E4-terminalarea)
Analoginputterminalsensorburnout
Checkwiringandsensor.
Errorindicationiserasedinnormal
operation.
Setupparameter(PV1.E/PV2.E)
PVinputburnouterror(Loop1,
Loop2)
BurnoutofanaloginputconnectedtoPV
Checkwiringandsensorofconnected
analoginputterminals.
Errorindicationiserasedinnormal
operation.
OVER
-OVER
Normalindication Setupparameter(PV1.E/PV2.E)
PVinputover-scale
PVinputunder-scale
(PVvaluesoutof-5to105%)(Loop
1,Loop2)
PVinputisoutof-5to105%.Alsooccurs
whenthedataoutofrangewhichisthe
ladder calculation result is input.
Checkanaloginputvalueorladder
program.
Normal
indication
Normalindication Setupparameter(PV1.E/PV2.E)
RSPinputburnouterror(Loop1,
Loop2)
BurnoutofanaloginputconnectedtoRSP
Checkwiringandsensor.Error
indication is erased in normal operation.
Normal
indication
RSPB.OUT
Setupparameter(PV1.E/PV2.E)
BurnouterrorwhenRSPinputis
usedforcontrol(Loop1,Loop2)
BurnoutofanaloginputconnectedtoRSP
whenRSPisusedforcontrolcomputation
Checkwiringandsensor.Error
indication is erased in normal operation.
Normal
indication
OUT-----
Setupparameter(AD2.E)
Feedbackinputresistor/current
burnout
Feedbackinputburnout
Checkwiringoffeedbackinputresistor/
current.Errorindicationiserasedin
normal operation.
Normal
indication
Normalindication LADDERlampblinks Setupparameter(LA.ER)
Laddercalculationoverow
Floatingpointcomputationforladder
calculationisinnite.
Checktheladderprogram.
Loadfactorover100%
Computationdoesnotendwithinthe
controlperiod(loadfactoris100%or
more).
Changethecontrolperiodorreduce
thenumberofstepsfortheladder
program.
Loadfactorover200%
(Forcedend)
Computationdoesnotendwithinthecontrol
period(loadfactoris200%ormore).
Changethecontrolperiodorreducethe
numberofstepsfortheladderprogram.
Ladderprogramerror Ladderprogramiscorrupted.
Downloadtheladderprogramagain.If
theerrorindicationisstillnoterased,
thereisafault.Contactusforrepair.
0.00000000
(Decimalpointontheleftof
theSymboldisplayblinks)
Setupparameter(OP.ER) Peer-to-peercommunicationerror Peer-to-peercommunicationerror
Checkthatthetargetdevicesare
connected correctly.
Recoveryatnormalreceipt.
AT.E
Normalindication Setupparameter(PV1.E/PV2.E)
Auto-tuningtime-out
(Loop1,Loop2)
Auto-tuningdoesnotendevenwhen24
hourshaveelapsedafterthestartoftuning.
Checktheprocess.Holddownanykeyto
erase the error indication
VAT.E
Normalindication Setupparameter(AD2.E)
Valvepositionautomatic
adjustmenterror
Fully-closedvalvepositionisequaltoorlarger
thanthefully-openvalvepositionafterautomatic
valvepositionadjustmentisperformed.
Checkwiringandvalve.Holddownany
key to erase the error indication.
Normal
indication
0.00000000
(Decimalpointontheleftof
theSymboldisplayblinks)
Setupparameter(OP.ER)
Communicationerror
(RS-485communication)
Framingparityerror
Bufferoverow
Inter-charactertime-out
Checksumerror(PClinkcommunicationwith
checksum)
CRCcheckerror(Modbus/RTU)
LRCcheckerror(Modbus/ASCII)
Checkthecommunicationparameters.
Recoveryatnormalreceipt.
Holddownanykeytostopblinking.
Normal
indication
0.00000000
(Decimalpointontheleftof
theSymboldisplayblinks)
Setupparameter(OP.ER)
Communicationerror
(coordinatedoperation)
Inconsistenceofloopbetweencoordinated
masterandslaves
Checkthecommunicationparameters.
Recoveryatnormalreceipt.
Changefromremotetolocalmodetostop
blinking.
Whenthemodeischangedfromremoteto
local,SPtrackingdoesnotworkevenifitis
settoON.
Communicationfromcoordinatedmasteris
interrupted for 2 seconds.
Normal
indication
0.00000000
(Decimalpointontheleftof
theSymboldisplayblinks)
Setupparameter(OP.ER) Userproleerror Userproleiscorrupted. Downloadtheuserproleagain.
Normal
indication
Normalindication
Rightmostdecimalpointon
Symboldisplayblinks.
Setupparameter(PA.ER) FaultyFRAM
Writing(storing)datatoFRAMisimpossible.
Faulty.Contactusforrepair.
Undened Undened
FaultyMCU/DCU
(ROM/RAMerror,corrupted)
MCU/DCUiscorrupted. Faulty.Contactusforrepair.
Note:WhenanerroroccursininputshowninAnaloginputdisplay(Operationdisplay),SetpointdisplayshowsthesamesymbolasthePVdisplay.

Other manuals for YOKOGAWA UT52A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA UT52A and is the answer not in the manual?

YOKOGAWA UT52A Specifications

General IconGeneral
BrandYOKOGAWA
ModelUT52A
CategoryController
LanguageEnglish

Related product manuals