FORM 100.50-NOM7 (808)
13
JOHNSON CONTROLS
1
Static Pressure Control Plastic Tubing 
(Pneumatic Tubing)
Duct static transducers (all VAV and FLEXSYS units) 
and any unit with an optional building pressure control 
transducer,  require pneumatic  tubing  to  be  eld sup-
plied and installed. The “High” side of the respective 
transducer must be routed to the location in the building 
or ductwork where a constant pressure is desired. Duct 
pressure transducer is located next to the supply VFD.
Duct Static Transducer
Plastic  tubing  (3/16"  ID)  must  be  run  from  the  high 
pressure tap of the transducer to a static pressure tap 
(eld supplied) in the supply duct, located at a point 
where constant pressure is desired.
Building Pressure Transducer
Plastic  tubing  (3/16"  ID)  must  be  run  from  the  high 
pressure tap of the building static pressure transducer 
to a static pressure tap (eld supplied), located in the 
conditioned space or return air duct at a point where 
constant pressure is desired.
Static Pressure Probe Installation
On units with duct static transducers (VAV units) and 
any unit with an optional building pressure, a Static 
Pressure Probe must be eld installed at the top of the 
rear corner post on the unit.
The factory supplied atmospheric pressure probe and 
associated mounting hardware are shipped inside the 
unit control panel. The hardware consists of a mounting 
bracket and a short section of pneumatic tubing. The 
pneumatic tubing must be eld installed from a fac-
tory pressure tap (next to the mounting location for 
the static pressure probe) to the atmospheric pressure 
probe.
 
If the unit is equipped with both a building pressure 
transducer and a duct static transducer, there will be two 
pressure taps that are factory installed in the location 
where the factory supplied atmospheric pressure probe 
is to be mounted. A “tee” will be factory installed, and 
both the duct static pressure transducer and building 
pressure will be connected to the “tee” - both building 
static pressure transducer and duct static transducer 
will use the same factory supplied atmospheric pres-
sure probe.