100
YORK INTERNATIONAL
FORM 201.19-NM8 (804)
Technical Data
FIG. 53 – MODEL YCAS1065 - YCAS1215 (SI)
DIMENSIONS – YCAS1065 - YCAS1215 (SI)
All dimensions are in 
mm  un less  oth er wise 
noted.
NOTES:
1.   Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, re li able 
operation and ease of maintenance. Site re stric tions may compromise min i mum clearances indicated below, resulting in un pre dict able air ß ow 
pat terns and possible di min ished performance. YORK’s unit controls will optimize operation without nui sance high pres sure safety cutout; 
however, the system designer must con sid er potential performance degradation. Access to the unit control center assumes the unit is no 
higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; con trol panel end to wall - 1.2m; top 
- no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be higher than the unit.
48
2235
2331
1067
800
51
178
191
B
B
540
(12) 13
305
711
51 TYP.
229
51
120
C
C
VIEW A-A
OPENING
(229 HIGH)
OPENING
(533 HIGH)
CONTROL
POWER
VIEW C-C
CONTROL ENTRY
CONDUIT K.O.’S
VIEW B-B
CONTROL CENTER
MICROCOMPUTER
OPTIONS PANEL
CONNECTION)
BASE TO COOLER
78 (EDGE OF
CONTROL
TRANSFORMER
SERVICE SWITCH
LD06107