Closed:
Low Ambient Mode allows the Low Ambient Cut-Out 
to be programmed from 0 to 50 °F (-18 to 10°C). Val ues 
above 25°F (-4°C) can be used to automatically shut 
down the chiller when direct cooling methods be come 
operational.
SWITCH 3: Refrigerant 
Open:
The R-407C Mode MUST be selected for models us ing 
refrigerant R-407C. Incorrect selection of this switch 
may cause serious damage to the chiller.
Closed:
The R-22 Mode MUST be selected for models using 
refrigerant type R-22. Incorrect selection of this switch 
may cause serious damage to the chiller.
SWITCH 4: Unit Type 
Open:
DO NOT USE THIS POSITION.
Incorrect programming may cause 
damage to the chiller.
Closed:
Place the switch in the CLOSED position selects the 
type of chiller as an air cooled chiller (YCAS).  The 
switch MUST always be in the CLOSED position.
Incorrect programming may cause 
damage to the chiller.
S  1 - 2  A  M B I   E  N  T      C O N  T  R O  L
  L  O W   A M B  I E N  T
S  1 -  3  R E  F R  I  G E  R  A N  T
                               R  -  4  0   7 C
S  1 -  3  R E  F R  I  G E  R  A N  T
 R  - 2  2
Dip Switch Physical Location and Setting
FIG. 77 – ENLARGED PHOTOGRAPH OF DIP   
SWITCHES ON MICROPROCESSOR BOARD
LD03511A
LD03511B
“OPEN” Position: 
Left side of switch 
pushed in
“CLOSED” Position:
Right side of switch 
pushed in
8
S  1 -  4   Y C W S  
S  1 -  4   Y C A S  
SWITCH 5: Motor Current Average option 
                      (start-up)
Open:
DO NOT USE THIS POSITION.
Nuisance trips at start-up could result.
S  1 -  5      M O T O R   C U R R E N T
A V E R A G I N G   E N A B L E D
028981-G