174
YORK INTERNATIONAL
FORM 201.19-NM8 (804)
Key in the desired Chilled Liquid Setpoint and the 
al low able deviation (Range). The micro will accept 
val ues from 10.0 - 70.0°F (-12 to 21°C). For values 
below 40°F (4.4°C), Dip Switch S1, Switch #1 on the 
Mi cro pro ces sor  Board  must  be  properly  programmed 
for Glycol Cooling (see Section 3.7). If unacceptable 
val ues are entered, or the switch is incorrectly selected 
when setpoints below 40°F (4.4°C) are entered, the fol-
 low ing message will be displayed before returning to 
the Con trol Range message:
After the Setpoint is keyed in, the cursor will au to mat i-
 cal ly advance to the fi rst digit of the Range as shown:
This value should be programmed for the maximum de-
sirable positive and negative chilled liquid tem per a ture 
deviation that is acceptable from setpoint for the system 
application. A typical value would be +/- 2.0°F (1.1°C). 
The micro will accept a range from 1.5 - 2.5°F (0.9 to 
1.4°C). 
After the Setpoint and Range is keyed in, press the 
ENTER Key to store the data in memory.
Failure to press the Enter key will 
cause the new ly programmed values 
to be ig nored and not en tered into 
mem o ry.
After pressing the Enter key, the display will continue 
to show the message until another key is pressed.
6.4  REMOTE COOLING SETPOINTS KEY
Remote Cooling Setpoints key allows resetting the set-
 point upward from the programmed value in mem o ry 
from a remote device. This feature is typically used for 
demand limiting or ice storage applications. Reset is 
accomplished by timed closure of external con tacts for 
a defi ned period of time and allows reset of the set point 
upward by up to 40°F (22°C) above the setpoint pro-
 grammed in memory – see Section 1.7.
The maximum allowable reset must be programmed into 
memory and can be a value of 2 to 40°F (1 to 22°C) de-
pending on user requirements. To program the maximum 
reset, press the Remote Reset Temperature Range key. 
The following message will appear: 
The display indicates the Remote Setpoint which is 
al ways equal to the chilled liquid setpoint programmed 
by the Chilled Liquid Temperature/Range key plus the 
off set from the remote reset signal. The display will also 
show the Range which is the programmed max i mum de-
viation allowed for the application. The RANGE dis play 
is not programmable, and only the setpoint will change  
as a result of a signal from a remote device. 
Pressing the REM RESET TEMP RANGE Key again 
scrolls the display to the MAX EMS-PWM REMOTE 
TEMP RESET which is programmable. This should be 
programmed to the maximum offset which is required 
for the application. The maximum programmable val ue 
is 40° F (22°C), while the minimum programmable val ue 
is 2°F (1.1°C).
The cursor will stop beneath the fi rst digit of the max-
 i mum reset. Key in the maximum reset allowed for the 
application, remembering to use a leading “0” for val ues 
less than 10°F (or 5.6°C). Press the ENTER Key to store 
the new value in memory.
O U  T      O  F R A  N G E -
 T  R  Y      A G A   I  N  !
S  E  T  P O I   N  T  =   4  4  .   0       °   F  
 R A N G E      =  +   / -  2
 .   0  °   F
R E M  S E  T  P  =   4  4  .   0  °  F  
 R A N G E      =  +   / -  2  .   0       °   F
 M A X  E  M S  -   P W M      R E M O T  E  
 T  E  M P  R  E S  E  T  =   +  4  0   °  F
OIL TEMPERATURE ANTICIPATORY SHUTDOWN 
CONTROL
If the oil temperature nears the safety shutdown point, 
the micro may turn off the compressor to avoid a high 
oil temperature fault.
If the oil temperature rises above 220ºF (104ºC) and 
SV position is <60 steps, the micro will pump down the 
compressor and shut it off.  The micro will not allow the 
affected system to restart for a period of 15 minutes.  A 
message indicating the compressor start inhibit will be 
displayed.  An example of the display is shown below.
6.3  LOCAL COOLING SETPOINTS KEY
The Local Cooling Setpoints key is used to program the 
required Leaving Chilled Liquid control tem per a tures 
for the application. When the key is pressed,  the fol-
 low ing message will be displayed:
S  E  T  P O I   N  T  =   4  4  .   0       °  F  
 R A N G E      =  +   / -  2  .   0       °   F
Micro Panel Contents
S  Y S      #    D  S  C  H     /  O  I  L     I  N  H  I  B
S  Y S      #    D  S  C  H     /  O  I  L     I  N  H  I  B