the switches is important during the com mis sion ing of 
the chiller. The Options key can be used to verify the 
Dip Switch positions without looking at or handling the 
Microprocessor Board.
Each press of the key will scroll to the next option/dip 
switch setting.  Option Switch Messages (S1-1 to S1-
8) will then be displayed in sequence. At the end of the 
sequence, the display will automatically revert to the 
fi rst Option Switch message.
The following is a detailed guide to programming the 
Dip Switches together with the associated display mes-
 sage provided for each selection when the Options key 
is pressed:
SWITCH 1: Water / Glycol Cooling
Open:
Water Cooling Mode is for water cooling applications 
and allows the chilled liquid leaving temperature set-
 point to be programmed from 40 to 70 °F (4 to 21°C). 
Se lect ing this mode also auto-programs the Low Chilled 
Liq uid Cut-Out at 36°F (2°C) and the Suction Pressure 
Cut-Out at 44 PSIG (3 bar).
Closed:
Glycol Cooling Mode is for brine/glycol applications with 
setpoints below 40°F (4°C) and allows the chilled liquid 
leaving temperature setpoint to be programmed from 10 to 
70°F (-12 - 21°C). In this mode, the Low Chilled Liq uid 
Cut-Out can be programmed from 8 to 36° F (-13 to 2°C) 
and the Suction Pressure Cut-Out programmed from 20 
to 70 PSIG (1 to 5 bar) for R-22 models and 5 to 70 PSIG 
(0.3 to 5 bar) for R407C mod els.
SWITCH 2: Ambient Temp. Range Low Ambient 
Cutout
Open:
Standard Ambient Mode auto-programs the Low Am bi ent 
Cutout setting at 25°F (-4°C) and is not ad just able.
S  1 - 2  A  M B I   E  N  T      C O N  T  R O  L
 S  T  A N D  A R  D
3.5  % MOTOR CURRENT KEY
Pressing the Motor Current key displays compressor 
current for each system:
This display shows the average motor current in amps 
and average compressor motor current as a percentage 
of FLA. All values are approximate. 
On the second press of the of the Motor Current Key, 
the current limit values as set by the ISN (Remote BAS 
System) and EMS-PWM current limiting input are 
dis played, if they are active. See Sections 1.10, and 2.4  
for more details. 
3.6  OPERATING HRS / START COUNTER KEY
When the Operating Hours / Starts Counter key is 
pressed, the accumulated running hours and starts for 
System 1 and 2 compressors are displayed. Where ap-
 pli ca ble, pressing the key again displays the values for 
Systems 3 and 4 on larger models:
Display Limits :   Maximum run hours 99,999
   Maximum starts 99,999
Values roll over to zero, if the maximum limit is ex-
 ceed ed.
These counters are zeroed at the fac-
 to ry, but may in di cate run time and 
number of starts logged dur ing fac-
 to ry testing prior to shipment.
3.7  OPTIONS KEY & DIP SWITCH SETTINGS
The Options key provides a display of op tions which are 
programmed by the po si tions of the S1 Dip Switch es 
on  the  Mi cro pro ces sor  Board.  Proper  pro gram ming  of 
H R S      1  = 1  1  4  3 .   2      = 1   3  8  2
S  T R  1  =  2 8  5  .   2      = 3  2  2
H R S      3  = 1  2  5  5 .   4      = 1   0  9  5
S  T R  3  =  3 6  5  .   4      = 4  5  5
  S  1 - 1   C  H I   L  L E  D  L I  Q U I  D
  W A  T  E R
S  1 -  1  C H   I   L  L  E D      L  I  Q U  I  D
  G  L  Y  C O L
C O M P   1  =  6   3  A M P   8  5  % F  L  A
C O M P   2  =  3   0  A M P   4  1  % F  L  A
I S N      C R N  T  L   I M  I T  :   N O  N  E
E M  S      C R N  T  L   I M  I T  :   N O  N  E