164
YORK INTERNATIONAL
FORM 201.19-NM8 (804)
The System Evaporator Inlet Refrig-
erant Tem per a ture will be printed if 
the unit is in R407C mode.
SUCTION SUPERHEAT        3.4 DEGF
SAT DISCHARGE TEMP      74.5 DEGF
DISCHARGE SUPERHEAT      6.3 DEGF
SLIDE VALVE STEP                0
EEV OUTPUT                  0.0 %
EVAPORATOR INLET REFRIG  44.6 DEGF
LIQUID LINE SOLENOID          OFF
ECONOMIZER TXV SOLENOID       OFF
CONDENSER FAN STAGE           OFF
COMPRESSOR HEATER              ON
WYE-DELTA RELAY               OFF
     SYSTEM 2 DATA
COMPRESSORS STATUS             ON
RUN TIME       0- 0-15-26 D-H-M-S
MOTOR CURRENT    104 AMPS 87 %FLA
SUCTION PRESSURE          57 PSIG
DISCHARGE PRESSURE       233 PSIG
OIL PRESSURE             218 PSIG
SUCTION TEMPERATURE     42.9 DEGF
DISCHARGE TEMPERATURE  145.5 DEGF
OIL TEMPERATURE        102.8 DEGF
SAT SUCTION TEMP        31.7 DEGF
SUCTION SUPERHEAT       11.2 DEGF
SAT DISCHARGE TEMP     112.1 DEGF
DISCHARGE SUPERHEAT     33.4 DEGF
SLIDE VALVE STEP               70
EEV OUTPUT                 35.6 % 
EVAPORATOR INLET REFRIG     23.6 DEGF 
LIQUID LINE SOLENOID           ON
ECONOMIZER TXV SOLENOID        ON
CONDENSER FAN STAGE             3
COMPRESSOR HEATER             OFF
WYE-DELTA RELAY                ON
     DAILY SCHEDULE
S M T W T F S       *=HOLIDAY
MON START=00:00AM  STOP=00:00AM
TUE START=00:00AM  STOP=00:00AM
WED START=00:00AM  STOP=00:00AM
THU START=00:00AM  STOP=00:00AM
FRI START=00:00AM  STOP=00:00AM
SAT START=00:00AM  STOP=00:00AM
HOL START=00:00AM  STOP=00:00AM
Micro Panel Contents
4.5   HISTORY KEY
If a safety shutdown occurs on the chiller, a com pre -
hen sive list of operating and programmed settings data 
is stored by the microprocessor. The information is 
stored at the instant of the fault, regardless of whether 
the fault caused a lockout to occur. This information is 
not af fect ed by power failures or manual resetting of a 
fault lockout. 
The microprocessor stores data for up to 6 safety shut-
 downs on 2 System units and 4 safety shutdowns on 
3 or 4 compressor units. Once this limit is reached, a 
fur ther shutdown will cause the oldest set of data to be 
discarded in favor of storing the new shutdown data. The 
Safety Shutdowns are numbered from 1 to 6 or 1 to 4 
with num ber 1 always being the most recent.
If a remote printer is not connected, pressing the His-
 to ry key allows the operator to locally scroll through 
in for ma tion relating to the stored safety shutdowns on 
the con trol panel display. 
If a remote printer is connected, pressing the History key 
will cause data from the last 6 shutdowns on a 2 com-
pressor chiller or 4 shutdowns on a 3 or 4 com pres sor 
chiller to be transmitted from the mi cro pro ces sor to the 
remote printer. The printout will begin with the most 
recent fault which occurred. This does not affect the 
stored data and as many prints as desired may be tak en. 
See Section 4.7 for a HISTORY printout sample.
4.6  FAULT HISTORY DATA –
 
LOCAL DISPLAY MESSAGES
When the History key is pressed, the following mes sage 
will appear:
To select a Safety Shutdown, press the appropriate key 
on the numeric key pad, then press Enter. Remember that 
the most recent fault information is stored as shut down 
No. 1. After the ENTER Key is pressed, a mes sage in-
dicating the time and date of the Fault Shut down will 
appear:
 S H U  T D O W N   O C  C  U R  R  E D
 5 :  5  9 A M          2  9   N O V       0  2
D  I   S  P  L A  Y  S  A  F E  T  Y  S H U  T   -
D O W N  N O  .   1  (  1 T O  4   )