ELECTRICAL NOTES
Technical Data
NOTES
 1.    MRA is Maximum Running Amps, the maximum continuous current at any operating point in the rating range. Also referred to as MCA, or 
Minimum Circuit Ampacity to be provided by the installer. If a Factory Mounted Control Transformer is provided, add 3 amps to the system 
#1 MCA values in the YCAS Tables.
 2.   The recommended disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the 
circuit, per N.E.C. 440 - 12A1.
 3.   Minimum recommended fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs. Minimum fuse rating = 
(1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
 4.    Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit, 
per N.E.C. 440-22. Maximum fuse rating  = (2.25 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
 5.   Minimum recommended circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit. Minimum circuit breaker 
rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
 6.  Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per 
U.L. 1995 Fig. 36.2. Maximum circuit breaker rating = (2.25 x largest compressor RLA) + other com pres sor RLAs + ( # fans x each fan motor 
FLA).
 7.    The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs.  The (1), (2), or (3) 
indicate the number of termination points or lugs which are available per phase.  Actual wire size and number of wires per phase must be 
determined based on ampacity and job requirements using N.E.C. wire sizing information.  The above recommendations are based on the 
National Electrical Code and using copper connectors only. Field wiring  must also comply with local codes.
  8.    A ground lug is provided for each compressor system to accommodate Þ eld grounding conductor per N.E.C. Article 250-54. A control circuit 
grounding lug is also supplied.
 9.  The Þ eld supplied disconnect is a “Disconnecting Means” as deÞ ned in N.E.C. 100.B, and is intended for isolating the unit from the available 
power supply to perform maintenance and troubleshooting.  This disconnect is not intended to be a Load Break Device.
10.   Two-compressor machines with single-point power connection, and equipped with Star-Delta compressor motor start must also include 
Factory provided circuit breakers in each motor control center.
11.   Consult factory for Electrical Data on units equipped with “High Static Fan” option.  50Hz High Static Fans are 3.5kW each.
12.   FLA for each “Low Noise Fan” motor:   380v/50Hz = 4.1A.
 ACR-LINE      ACROSS THE LINE START
  CB CIRCUIT BREAKER
  DE FU DUAL ELEMENT FUSE
 DISC SW DISCONNECT SWITCH
  FACT MOUNT CB FACTORY-MOUNTED CIRCUIT BREAKER
  FACT MOUNT FUSE FACTORY-MOUNTED FUSES
 FLA     FULL LOAD AMPS
  HZ HERTZ
  MAX MAXIMUM
  MCA     MINIMUM CIRCUIT AMPACITY
 MIN MINIMUM
 MIN NF MINIMUM NON-FUSED
  RLA     RUNNING LOAD AMPS
                                                S.P. WIRE SINGLE-POINT WIRING
 UNIT MTD SERV SW UNIT-MOUNTED SERVICE (NON-FUSED DIS CON NECT SWITCH)
  WYE-DELTA     WYE-DELTA START
  XLRA     ACROSS-THE-LINE INRUSH LOCKED ROTOR AMPS
  YLRA     WYE-DELTA INRUSH LOCKED ROTOR AMPS
LEGEND