FIG. 40 – ELEMENTARY DIAGRAM 4 COMPRESSOR
LD010045
CAUTION:
No Controls (relays, etc.) should be mount ed in the Smart Panel 
en clo sure  or  con nect ed to pow er sup plies in the control pan el. Ad-
ditionally, con trol wir ing not con nect ed to the Smart Panel should not 
be run through the cabinet. This could re sult in nui sance faults.
CAUTION:
Any inductive devices (re lays) wired in series with the fl ow switch 
for start/stop, into the Alarm cir cuit ry, or pilot relays for pump 
start ers wired through mo tor contactor aux il ia ry con tacts must be 
sup pressed with YORK P/N 031-00808-000 sup pres sor across the 
re lay/contactor  coil. 
 
UNIT
  CONTROL MIN           MAX DUAL      NON-FUSED
 
VOLTAGE
  POWER  CIRCUIT  ELEMENT             DISC.
 SUPPLY AMP.           FUSE SIZE  SWITCH SIZE
 ALL MODELS 
115-1-50/60 20A  20A 250V           30A 240V
  W/O TRANS.
  MODELS         -17 200-1-60  15A  15A 250V           30A 240V
  WITH            -28 230-1-60  15A  15A 250V           30A 240V
  TRANS.          -46 400-1-60  8A  8A 600V            30A 480V
  * -58 575-1-60  8A  8A 600V            30A 600V
* All primary and secondary wiring between transformer and control panel in clud ed.
CONTROL POWER SUPPLY
Any contacts con nect ed to fl ow switch inputs or BAS in puts on 
ter mi nals 13 - 19 or TB3, or any oth er ter mi nals, must be sup-
 pressed with a YORK P/N 031-00808-000 sup pres sor across the 
re lay/con tac tor  coil.
CAUTION:
Control wiring con nect ed to the con trol panel should nev er be run in 
the same con duit with pow er wir ing.