INSTALLATION INSTRUCTIONS FOR
VMC SERIES AWR/AWMR AND CP
RESTRAINED MOUNTINGS
1.    Floor should be level and smooth.
2.    For indoor applications, isolators do not nor mal ly 
re quire bolting. If necessary, anchor iso la tors to 
fl oor through bolt holes in base plate. 
 IM POR TANT: Iso la tors must be bolted to 
sub struc ture  and  equip ment to isolators when 
used under outdoor equip ment exposed to wind 
forc es.
3.    Lubricate threads of adjusting bolt. Loosen hold 
down bolts to allow for isolator adjustment.
4.    Block the equipment 1/4" higher than the spec-
 i fi ed free height of the isolator. To use the iso la tor 
as block ing for the equipment, insert a 1/4" shim 
be tween the upper load plate and vertical up rights. 
Lower the equip ment on the blocking or shimmed 
isolators.
5.    Complete piping and fi ll equipment with wa ter, 
re frig er ant,  etc.
6.    Turn leveling bolt of fi rst isolator four full rev o -
lu tions and proceed to each mount in turn.
7.     Continue turning leveling bolts until equip ment is 
fully supported by all mountings and equip ment is 
raised free of the spacer blocks or shims. Remove 
blocks or shims.
8.    Turn leveling bolt of all mountings in either di-
 rec tion in order to level the installation.
9.    Tighten nuts on hold down bolts to permit a clear-
 ance of 1/8" between resilient washer and un der side 
of channel cap plate.
10.  Installation is now complete.