41
YORK INTERNATIONAL
FORM 201.19-NM8 (804)
5
Check that the tapping used conforms to the site sup ply 
voltage. After the tapping is verifi ed, replace the lid.
Switch Settings
Ensure that the unit ON/OFF switch on the display door 
and the micro board system switch es S2 through S5 are 
set to “0” (OFF). Set the red han dled emergency stop 
de vice on the options panel to “1” (ON). For units fi tted 
with door interlocked circuit breakers the power panel 
doors must be closed and the devices set to “1” (ON). 
The customer’s power dis con nec tion devices can now 
be set to ON.
The machine is now live!
The unit is fi tted with an under voltage circuit in each 
pan el and it may take be tween 5 to 10 seconds for its 
con tacts to close and energize the unit’s electronics, 
in clud ing the dis play on the main panel.
Compressor Heaters
Verify the compressor heaters are en er gized.  If the am-
bient temperature is above 96°F (36°C) the com pres sor  
heaters must be on for at least 8 hours before start-up to 
ensure all refrigerant liquid is driven out of the compres-
sor.  If the ambient tem per a ture is be low 86°F (30°C) 
then allow 24 hours.
Water System
Verify that the chilled liquid system has been installed 
correctly, and has been commissioned with the correct 
direction of water fl ow through the evaporator. The inlet 
should be at the refrigerant pipework connection end of 
the evaporator. Purge air from the top of the evaporator 
using the plugged air vent mounted on the top of the 
evaporator body. Flow rates and pressure drops must be 
within the limits given in the Technical Data Section. 
Op er a tion  outside  of  these  lim its  is  un de sir able  and  could 
cause damage.
Flow Switch
Verify a chilled water fl ow switch is cor rect ly fi tted in 
the customer’s pipework on the evaporator outlet, and 
wired into the control panel correctly using shielded 
cable. There should be a straight run of at least 5 pipe 
di am e ters on either side of the fl ow switch. The fl ow 
switch should be connected to terminals 13 and 14 in the 
mi cro panel (Figs. 13 and 14, pages 38 and 39).
Temperature sensor(s)
Ensure the leaving liquid tem per a ture sensor is coated 
with heat conductive com pound (part no. 013-00890-
000) and is inserted in the water outlet sensor pocket 
of the evaporator. This sensor also acts as the freeze 
pro tec tion ther mo stat sensor and must always be in the 
water OUTLET sen sor pocket.
Control Supply
Verify the control panel display is illuminated.
Programmed Options
Verify that the options factory programmed into the 
Mi cro com put er Control Center are in accordance with 
the cus tom er’s order re quire ments by pressing the ‘Op-
 tions’ key on the keypad and read ing the settings from 
the display.
 
Programmed Settings
Ensure the system cut-out and operational settings 
are in accordance with the in struc tions provided in 
Sec tion 8 (page 178) and with the general chiller op-
 er a tion al  re quire ments  by  press ing  the  ‘Pro gram’  key. 
The  chilled  liquid  tem per a ture  con trol  set tings  need  to 
be set ac cord ing to the unit model and required op er -
at ing  con di tions.
 
Date and Time
Program the date and time by fi rst en sur ing that the CLK 
jumper J18 on the mi cro pro ces sor board is in the ON 
position (top two pins). Then press the ‘Clock Set Time’ 
key and set the date and time. (See Section 7.)
Start/Stop Schedule
Program the daily and hol i day start/stop by pressing the 
‘Set Schedule/Holiday’ key. (See Section 7.)
Setpoint and Remote Offset
Set the required leav ing chilled liquid temperature 
set point and control range. If remote temperature reset 
(off set) is to be used, the maximum reset must be pro-
 grammed by pressing the ‘Remote Reset Temp’ key. 
(See Section 6.)