76
YORK INTERNATIONAL
FORM 201.19-NM8 (804)
FIG. 38 – ELEMENTARY WIRING DIAGRAM
NOTES:
1.  Field wiring to be in accordance with the current edi tion of 
the National Electrical Code as well as all oth er ap pli ca ble 
codes and specifi cations.
2. Contacts must be suitable for switching 24VDC, (Gold 
contacts recommend).  Wiring shall not be run in the same 
conduit with any line voltage wiring.
3. To cycle the unit on and off automatically with contact 
shown, install a cycling device in series with the fl ow 
switch (FLSW).  See note 2 for contact rating and wiring 
specifi cations.
4. To stop unit (Emergency Stop) with contacts other than 
those shown, install the stop contact between terminals 5 
and 1.  If a stop device is not installed, a jumper must be 
connected between terminals 5 and 1.  Device must have 
a minimum contact rating of 100A at 115 volts A.C.
5.  Alarm contacts are for annunciating alarm/unit malfunc-
tion.  Contacts are rated at 115V, 100VA, load only, and 
must be suppressed at load by user.
6.  See Installation, Operation and Maintenance Manual when 
optional equipment is used.
LEGEND
Transient Voltage Suppression
Terminal Block for Customer Connections
Terminal Block for Customer Low Voltage
(Class 2) Connections. See Note 2
Terminal Block for YORK Connections Only
Wiring and Components by YORK
Optional Equipment
Wiring and/or Components by Others
T S
ELEMENTARY WIRING DIAGRAM (YCAS1065 - YCAS1215)
ACROSS-THE-LINE START
AND
WYE-DELTA START
LD09368
035-16253-103
Rev - A
035-16253-103
Rev A