202
YORK INTERNATIONAL
FORM 201.19-NM8 (804)
Micro Panel Contents
ISN
Page
Character Type DXST Chiller Data
P27 72-75 A Sys 2 Oil Pressure
P28 76-79 A Sys 2 Suction Pressure
P29 80-83 A Sys 2 Discharge Pressure
P30 84-87 A Sys 2 % Full Load Amps
P31 88-91 A Sys 2 Total Run Hours
P32 92-95 A Sys 2 Total Number of Starts
P33 96-99 A Sys 2 Anti-Recycle Timer
P34 100-103 A Sys 1 Evaporator Inlet Refrigerant Temp (R-407c only)
P35 104-107 A Sys 2 Evaporator Inlet Refrigerant Temp (R-407c only)
P36 108 Diital Chiller Run
P37 109 D Chiller Alarm
P38 110 D Evaporator Heater Status (YCAS)
P39 111 D Evaporator Pump Status
P40 112 D Hot Liquid Flow Switch (Heat Recovery)
P41 113 D
Sys 1 Spare
Sys 1 Discharge Cooling Solenoid Status (Euro CAT, Low Temp)
P42 114 D Sys 1 Liquid Line Solenoid Valve Status
P43 115 D
Sys 1 Economizer TXV Solenoid Status (YCAS)
Sys 1 Oil Cooling Solenoid Status (YCWS)
Sys 1 Condenser Solenoid Status (EURO CAT)
Sys 1 Heat Recovery Solenoid Status (Heat Recovery)
P44 116 D Sys 1 Wye-Delta
P45 117 D
Sys 2 Spare
Sys 2 Discharge Cooling Solenoid Status (Euro CAT, Low Temp)
P46 118 D Sys 2 Liquid Line Solenoid Valve Status
P47 119 D
Sys 2 Economizer TXV Solenoid Status (YCAS)
Sys 2 Oil Cooling Solenoid Status (YCWS)
Sys 2 Condenser Solenoid Status (Euro CAT)
Sys 2 Heat Recovery Solenoid Status (Heat Recovery)
P48 120 D Sys 2 Wye-Delta Relay
P49 121 D —
P50 122 D S1-1 Cooling Type: 0=Water, 1=Glycol
P51 123 D S1-2 Ambient Ctrl: 0=Standard, 1=Low Ambient
P52 124 D S1-3 Refrigerant Type: 0=R407c, 1=R-22
P53 125 D S1-4 Unit Type: 0=YCWS, 1=YCAS
P54 126 D S1-5 Motor Current Averaging: 0=Disabled, 1=Enabled
P55 127 D S1-6 Heat recovery: 0=Disabled, 1=Enabled
P56 128 Coded *Sys 1 Operational Code
P57 129 C *Sys 1 Fault Code
P58 130 C *Sys 2 Operatioanal Code
P59 131 C *Sys 2 Fault Code
P60 132 C Sys 1 Slide Valve Step
P61 133 C Sys 1 Condenser Fan Stages Running (0-6)
P62 134 C Sys 2 Slide Valve Step
P63 135 C Sys 2 Condenser Fan Stages Running (0-6)
P64 136 C Lead Compressor Number
P65 137 C Debug Code
TABLE 18 – ISN TRANSMITTED DATA (CONT'D)