YORK INTERNATIONAL
FORM 201.19-NM8 (804)
7
Excessive ow, above the max GPM,
will damage the evaporator.
TEMPERATURE AND FLOWS
(SI Units)
MODEL
LEAVING WATER
EVAPORATOR FLOW
AIR ON
NUMBER
TEMPERATURE (°C) (L/S)
3
CONDENSER (°C)
YCAS
MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
0685 5.0 13.0 18.5 67.6 -17.7 50
0775 5.0 13.0 21.0 76.0 -17.7 50
0835 5.0 13.0 21.0 76.0 -17.7 50
0905 5.0 13.0 21.0 76.0 -17.7 50
0965 5.0 13.0 21.0 76.0 -17.7 50
1065 5.0 13.0 27.2 101.0 -17.7 50
1135 5.0 13.0 27.2 101.0 -17.7 50
1215 5.0 13.0 27.2 101.0 -17.7 50
NOTES:
1. For leaving brine temperature below 5 °C, contact your nearest YORK ofÞ ce for application requirements.
2. For leaving water temperature higher than 13°C, contact the nearest YORK ofÞ ce for application guidelines.
3. The evaporator is protected against freeze-up to -28.8°C with an electrical heater as standard.