JOHNSON CONTROLS
141
SECTION 7 – UNIT CONTROLS
FORM 150.72-ICOM7
ISSUE DATE: 10/22/2020
7
035-02550-xxx I/O Board
FIGURE 33 - MICRO PANEL CONNECTIONS
LD14318
TABLE 19 - MINIMUM, MAXIMUM AND DEFAULT VALUES
DESCRIPTION MINIMUM MAXIMUM DEFAULT
DE MODIFIER ADDRESS -1 41943 -1
DE MODIFIER OFFSET -1 99 -1
P1 BAUD RATE 1200 76800 4800
1200, 4800, 9600, 19200, 38400, 76800, AUTO SELECTABLE
P2 BAUD RATE 1200 57600 1200
1200, 4800, 9600, 19200, 38400, 57600 SELECTABLE
P1, P2 MANUAL Mac
ADDRESS
-1 127 -1
P1, P2 PARITY NONE IGNORE NONE
NONE, EVEN, ODD, IGNORE SELECTABLE
P1 PROTOCOL BACNET API BACNET
BACNET, API SELECTABLE
P2 PROTOCOL TERMINAL MODBUS CLIENT API
TERMINAL, MODBUS IO, MODBUS SERVER, API, MODBUS CLIENT SELECTABLE
P1, P2 STOP BITS 1 2 1
RESET REAL TIME ERROR NO YES NO
The table below shows the minimum, maximum, and
default values.